IC698PSA100D
Description
1. General Description
1.1 Product Overview
1.2 Main Features
Universal AC/DC wide range input
100W rated total output power
Built-in active PFC, high power factor and high efficiency
Full protection: OVP, OCP, SCP, OTP, UVP
Hot-swappable and redundant parallel operation support
≤15ms seamless failover for redundant configuration
Front panel LED status indication and manual on/off control
Industrial grade design, suitable for harsh factory environment
Compliant with international safety, EMC and RoHS standards
2. Electrical Specifications
2.1 Input Characteristics
| Parameter | Rating |
|---|---|
| AC Input Voltage | 85 ~ 264 VAC |
| AC Frequency | 47Hz ~ 63Hz |
| DC Input Voltage | 100 ~ 150 VDC |
| Nominal Input | 120/240 VAC, 125 VDC |
| Power Factor | ≥ 0.99 (Active PFC) |
| Input Isolation | 1500VAC Input to Output |
2.2 Output Characteristics
| Output | Voltage Range | Max Current |
|---|---|---|
| +5VDC | 4.875 ~ 5.25VDC | 20A |
| +12VDC | 11.64 ~ 12.6VDC | 2A |
| -12VDC | -12.6 ~ -11.64VDC | 1A |
| Total Output Power | 100W @ 0°C ~ 60°C | — |
| Ripple & Noise | ≤ 120mV p-p | — |
| Line / Load Regulation | ±1% Typical | — |
| AC Line Ride-Through | ≥15ms | — |
3. Environmental & Mechanical Specifications
3.1 Environmental Conditions
| Item | Specification |
|---|---|
| Operating Temperature | 0°C ~ +60°C |
| Storage Temperature | -40°C ~ +85°C |
| Relative Humidity | 5% ~ 95% Non-condensing |
| Operating Altitude | Up to 2000m |
| Protection Grade | IP20 |
3.2 Mechanical Parameters
| Item | Specification |
|---|---|
| Installation | RX7i Chassis Slot 0 dedicated position |
| Module Type | Plug-in rack mount |
| Approx Weight | 0.9kg |
| Terminal Wire Gauge | Input: AWG16; Ground: AWG12 |
| Terminal Torque | 0.8 ~ 1.0 N·m |
4. Front Panel Indicators & Controls
4.1 LED Indicators
- PWR LEDON: Input voltage is normal within rated rangeOFF: No input power or input abnormal
- OK LEDON: All DC outputs normal, module working properlyOFF: Output abnormal or internal fault
- FAULT LEDON: Overvoltage, overcurrent, short circuit, over temperature or redundancy failure
4.2 On/Off Switch
5. Installation & Wiring Instructions
5.1 Installation Steps
Cut off the system power before installation and maintenance.
Insert IC698PSA100D into Slot 0 (the leftmost slot) of RX7i chassis.
Push the module firmly until fully engaged with backplane.
Fasten the front panel fixing screws.
Keep surrounding ventilation clearance ≥50mm, avoid heat source and sealed narrow space.
5.2 Wiring Requirements
AC wiring: Connect Line (L), Neutral (N), Protective Earth (PE) strictly.
DC wiring: Connect positive and negative polarity correctly, no reverse connection.
The module internal output is connected to backplane automatically, no external output wiring required.
All grounding points must be reliably connected to factory protective earth.
6. Redundant Configuration
6.1 Redundancy Mode
6.2 Failover Performance
Automatic fault detection and seamless switching
Switching time ≤15ms, no PLC system downtime or reset
When the faulty module is replaced and recovered, the system automatically re-establishes redundant backup.
7. Protection Functions
UVP: Under voltage protection
OVP: Over voltage protection
OCP: Over current protection
SCP: Short circuit protection
OTP: Over temperature protection
8. Maintenance & Troubleshooting
8.1 Daily Maintenance
Regularly clean dust on module surface and ventilation holes with dry compressed air every 3~6 months.
Check terminal tightness and grounding reliability periodically.
Adopt hot-swap replacement for faulty modules without stopping the system.
8.2 Common Troubleshooting
| Phenomenon | Possible Cause | Handling Method |
|---|---|---|
| PWR LED off | No input power / loose wiring | Check input voltage and re-tighten terminals |
| OK LED off | Overload / short circuit / internal failure | Reduce load, inspect I/O short circuit |
| FAULT LED always on | Over temperature / redundancy abnormal | Improve cabinet ventilation, check backup power module |
| Redundancy cannot switch | Backup module not powered or not seated | Reinstall backup module and check input power |
9. Safety & Compliance
Comply with IEC 61010-1, EN 61000 series EMC standards
UL 1012 certified, CE marked
RoHS environmental compliance
Do not disassemble the module; no user-serviceable internal parts