Description



2. Key Specifications
Model: EB401-10 (S1)
Function: ER Bus master interface
Physical Layer: IEEE 802.3 10BASE-2 (coaxial)
Connector: 1 × BNC
Communication Speed: 10 Mbps
Max. Distance: 185 m (with YCB141 cable)
Current Consumption: 0.7 A (≈6 W)
Weight: 0.3 kg
Dimensions (W×H×D): 32.8 × 130 × 144.5 mm
Installation: DIN-rail / rack-mount
Enclosure Rating: IP20
Operating Temperature: 0°C to +55°C
Storage Temperature: -20°C to +70°C
Humidity: 5%–95% RH (non-condensing)
Certifications: CE, UL, RoHS
3. Redundancy & Configuration
Dual Redundancy: Install two EB401-10 modules in the same host unit for redundant ER Bus operation (automatic failover <100 ms).
Single Configuration: Use one module in an odd-numbered slot of ANB10/AFF50; cover the adjacent slot with a dummy module (ADCV01).
Topology: Supports up to 4 ER Bus segments branched from the FCU.
4. Included Accessories
1 × T-connector (YCB146)
2 × Terminators (YCB148)
5. Diagnostic & Protection
Self-diagnostics: Real-time monitoring of power, communication, and hardware status.
LED Indicators: For POWER, RUN, RDY, ERR, COM status.
Protection: Overvoltage, overcurrent, short-circuit protection.
6. Application
System: CENTUM CS3000 (R3 and later)
Get a Quote