Yokogawa AAI143-S00
General Description
Specifications
Model: AAI143-S00
Type: Analog Input Module
Channels: 16, fully isolated
Input Signal: 4–20mA DC (max. 24mA)
HART Protocol: Not supported (key difference from H53)
Accuracy: ±16μA (typical)
Update Period: 10ms
Isolation Voltage: 1500V AC for 1 minute (input-to-system)
Transmitter Power: 19–25.5V DC (2-wire/4-wire compatible)
Operating Temperature: -10°C to +55°C (standard industrial)
Power Consumption: 230mA @5V; 540mA @24V
Dimensions/Weight: 107.5×32.8×130mm / 0.3kg
Certifications: CE, UL, CSA
Model Suffix Definition
S: Standard type
0: Basic type (no HART, no explosion protection, no wide temperature)
Key Features
High-Density Isolated Acquisition: 16 fully isolated channels for accurate 4–20mA measurement from temperature, pressure, flow, and level sensors.
Non-HART Design: Analog-only acquisition with lower cost, ideal for points without remote diagnostics needs.
Robust Isolation: High isolation between channels and input-to-system suppresses EMI/RFI for reliability in harsh environments.
Fast Response: 10ms high-speed sampling supports closed-loop control and real-time monitoring.
Standard Temperature Range: -10°C to +55°C for general control room environments.
Applications
DCS Systems: CENTUM CS 3000/VP series; seamless integration with Yokogawa platforms.
Process Industries: Chemical, oil & gas, power, water treatment, metallurgy for general parameter monitoring.
Sensor Interfacing: Connects 4–20mA transmitters (temperature, pressure, level, flow).
Cost-Effective Solutions: Dense I/O, no HART diagnostics, budget-sensitive projects.
Installation & Maintenance
Installation
Power off; use ESD protection (ground ≥1MΩ).
Mount on DIN rail or panel; torque to 0.8–1.2N·m.
Wiring: 2-wire/4-wire transmitters; shield ground at one end.
Power-on self-test: Green LED = normal; no alarms.
Maintenance
Daily: Check LED status, loose/corroded terminals.
Quarterly: Clean dust, verify torque.
Annual: Calibrate accuracy, assess aging; replace if needed.
Safety Precautions
Qualified personnel only: Installation, wiring, and maintenance per safety standards.
No hot swapping: Power off before insertion/removal to avoid damage and shock.
Alarm response: Power off immediately for faults; do not force restart.
Genuine parts: Use Yokogawa original components; non-genuine parts void performance and safety.