MVI56-104S
Description
1. Product Overview
Model: MVI56‑104S
Manufacturer: ProSoft Technology (inRAx series)
Platform: Allen‑Bradley ControlLogix (1756 chassis, single‑slot)
Protocol: IEC 60870‑5‑104 Server (Slave) (TCP/IP Ethernet for substation SCADA)
Function: Enables ControlLogix PLC to act as an IEC 104 server, exchanging data with IEC 104 client SCADA masters (electric utility control centers).
Data Exchange: 4000‑word internal register space between ControlLogix tags and Ethernet; supports time‑stamped events, TRBE (Report by Exception).
2. Key Features
Dual 10/100 Mbps Ethernet ports (P1, P2) for redundant network
IEC 104 server compliance: Supports ASDU types, time synchronization, TRBE
Client connections: Up to 8 concurrent IEC 104 clients
Data capacity: 4000 words (8000 bytes) shared I/O database
Event reporting: Unsolicited messages (spontaneous/cyclic) with millisecond time stamps
Diagnostic LEDs: PWR, RUN, BP LINK, P1 LINK/ACT, P2 LINK/ACT
Configuration: ProSoft Configuration Builder (PCB)
Approvals: CE, UL/cUL, CSA, ATEX, RoHS
3. Technical Specifications
General
Slot usage: 1 slot (1756 local/remote rack)
Backplane current: 800 mA @ 5 VDC
Data mapping: Direct tag access + 4000‑word shared database
Firmware: Field‑upgradeable via PCB
Ethernet Interface (P1/P2)
Standard: IEC 60870‑5‑104 (TCP/IP), 10/100Base‑TX
Connector: RJ45 (two ports, switchable redundancy)
Max clients: 8 simultaneous IEC 104 client connections
Data types: Analog, binary, counter, SOE, setpoints, parameters
Environmental
Operating temp: 0°C to +60°C (32°F to 140°F)
Storage temp: ‑40°C to +85°C
Humidity: 5%–95% non‑condensing
Vibration: 5 g (10–150 Hz)
Shock: 30 g (operational)
4. LED Indicators
PWR: On = backplane power OK
RUN: On = module operational; flashing = firmware activity
BP LINK: On = backplane communication active
P1/P2 LINK: On = Ethernet link established
P1/P2 ACT: Flashing = Ethernet data traffic
5. Installation & Configuration
Power off ControlLogix chassis.
Insert MVI56‑104S into empty 1756 slot.
Connect Ethernet cables to P1/P2; connect PC for configuration.
Power on; verify module in Studio 5000 I/O tree.
Use ProSoft Configuration Builder (PCB) to set:
Ethernet IP addresses, subnet, gateway
IEC 104 server parameters (ASDU, cause of transmission)
Tag mapping (ControlLogix tags ↔ 4000‑word database)
Download configuration; test with IEC 104 client simulator/SCADA.
6. Applications
Power substations: ControlLogix as IEC 104 server for SCADA master monitoring
Utility SCADA: Real‑time telemetry (analog/binary), SOE, fault recording
Renewable energy: Wind/solar farm data reporting to grid control centers
Water/wastewater: Remote plant monitoring via IEC 104 Ethernet
Petrochemical: Process data exchange with enterprise SCADA
7. Advantages
IEC 104 server for Rockwell: Native Ethernet integration for ControlLogix
Dual Ethernet redundancy: High availability for critical substation networks
Real‑time events: TRBE + millisecond time stamps for accurate SOE
Large data pool: 4000 words for extensive I/O and parameters
Seamless Rockwell workflow: Studio 5000 tags, no custom logic required
Get a Quote