MVI46-MBP
Description

1. Product Overview
Model: MVI46‑MBP
Manufacturer: ProSoft Technology
Platform: Allen‑Bradley SLC 500 (1746 backplane, single‑slot)
Protocol: Modbus Plus (MB+), peer‑to‑peer industrial network
Function: Enables SLC 500 PLCs to connect to Modbus Plus networks for bidirectional data exchange with Modicon PLCs, drives, relays, power monitors, and other MB+ devices.
2. Key Features
Dual‑port Modbus Plus interface (MB+ network, 57.6 kbps, no parity, 1 stop bit)
Peer‑to‑peer communication (master/slave supported)
4,000‑word shared data space between SLC and MB+ network via M0/M1 files
Up to 100 word read/write per transfer; global in/out: 0–32 words
Node address configurable 1–64; supports MB+ routing up to 5 levels
Asynchronous data transfer (SLC operations independent of MB+ network)
Ladder logic example included for M0/M1 data mapping
Diagnostic LEDs: Power, Run, Backplane, MB+ Link/Activity
3. Technical Specifications
General
Slot usage: 1 slot (1746 local/extended rack; remote rack not supported)
Backplane current: 300 mA @ 5 VDC
Data exchange: M0/M1 files (SLC memory access)
Modbus Plus Network
Baud rate: 57,600 bps (fixed)
Parity/stop bits: No parity, 1 stop bit
Max nodes: 64 per network segment
Function codes (slave): 1, 2, 3, 4, 5, 6, 15, 16
Environmental
Operating temp: 0°C to +60°C (32°F to 140°F)
Storage temp: -40°C to +85°C (-40°F to 185°F)
Humidity: 5%–95% non‑condensing
Vibration: 5 g (10–150 Hz)
Shock: 30 g (operational), 50 g (non‑operational)
4. LED Indicators
PWR: On = backplane power OK
RUN: On = module operational; flashing = firmware activity
BP LINK: On = backplane communication active
MB+ LINK: On = MB+ network connected
MB+ ACT: Flashing = MB+ data transmission
5. Installation & Configuration
Power off the SLC 500 chassis.
Insert MVI46‑MBP into an empty 1746 slot.
Connect MB+ network cable to the module’s MB+ port.
Power on the system; verify module recognition via RSLogix 500.
Configure node address (1–64) and MB+ parameters using the configuration tool.
Map SLC data (M0/M1 files) to MB+ registers via ladder logic.
Download configuration and test MB+ communication.
6. Applications
Connect SLC 500 to Modicon PLCs (Modbus Plus)
Integrate drives, relays, power monitors into SLC systems
Legacy SLC equipment networking upgrades
Factory‑wide Modbus Plus network monitoring
Industrial SCADA data collection via MB+
7. Advantages
Seamless SLC ↔ Modbus Plus integration
High‑speed, deterministic MB+ communication
Large 4,000‑word data buffer for complex data exchange
Robust industrial design for harsh environments
Proven compatibility with Rockwell Automation systems
Get a Quote