ILX69-PBM
May 18, 2026

ILX69-PBM

Model: ILX69‑PBM (ProSoft Technology) Platform: Rockwell CompactLogix™ 1769 chassis (single‑slot) Function: PROFIBUS DP Master (DPV0/DPV1) – connects CompactLogix to PROFIBUS DP slave devices Role: Acts as a PROFIBUS master, enabling cyclic + acyclic data exchange Certifications: PI‑certified, Rockwell Encompass approved

Description

ILX69-PBM.jpg

ILX69-PBM(2.jpg

1. Product Overview

  • Model: ILX69‑PBM (ProSoft Technology)

  • Platform: Rockwell CompactLogix™ 1769 chassis (single‑slot)

  • Function: PROFIBUS DP Master (DPV0/DPV1) – connects CompactLogix to PROFIBUS DP slave devices

  • Role: Acts as a PROFIBUS master, enabling cyclic + acyclic data exchange

  • Certifications: PI‑certified, Rockwell Encompass approved

2. Key Features

  • PROFIBUS DP Master: Supports DPV0 (cyclic) and DPV1 (acyclic, alarms)

  • Slave Capacity: Up to 125 slaves (some docs: 127)

  • Process Data:

    • Input: 5712 Bytes max

    • Output: 5760 Bytes max

  • Per‑Slave I/O: Up to 244 Bytes In / 244 Bytes Out per slave

  • Baud Rates: 9.6 kbps → 12 Mbps (auto‑detect)

  • DPV1 Services: Class 1 Read/Write, Class 1 Alarm, Class 2 Initiate/Read/Write

  • Ethernet Port: 10/100 Mbps RJ45 – for configuration & diagnostics (FDT/ComDTM)

  • SD Card Slot: Store configs, firmware updates (no CPU required)

  • Autoscan: Auto‑discover slaves, map addresses – reduces commissioning time

  • AOI Support: Add‑On Instructions for Studio 5000/RSLogix 5000

3. Technical Specifications

PROFIBUS Interface

  • Physical: RS‑485, RJ45 or terminal block

  • Protocol: PROFIBUS DP, DPV0/DPV1

  • Isolation: 2500 Vrms

Power

  • Source: 5 VDC from 1769 backplane

  • Current: 570 mA (≈2.5 W)

Environmental

  • Operating Temp: 0°C to +60°C (32°F to 140°F)

  • Storage Temp: ‑40°C to +85°C

  • Humidity: 5%–95% non‑condensing

  • Shock/Vibration: 30 g operational

Physical

  • Dimensions: ~124 × 57 × 32 mm (W × H × D)

  • Weight: ~0.23 kg (0.5 lb)

  • Mounting: 1769 chassis (DIN rail via base)

4. LED Indicators

  • PWR: Green = backplane power OK

  • STAT: Green = run; Red = fault

  • PBUS: Green = PROFIBUS activity; Red = network error

  • ETH: Green = Ethernet link; Flashing = activity

5. Typical Applications

  • Connect CompactLogix to PROFIBUS DP slaves (drives, I/O, meters)

  • Migrate legacy PROFIBUS systems to Rockwell CompactLogix

  • Process industries: water, power, chemical, automotive

  • Remote diagnostics via Ethernet (FDT/ComDTM)

6. Advantages

  • In‑chassis: No external gateway; native CompactLogix integration

  • DPV1 Full Support: Alarms & acyclic data for advanced devices

  • High Performance: 12 Mbps, large process data buffers

  • Easy Commissioning: Autoscan + AOI reduce programming effort

  • Remote Diagnostics: Ethernet port for troubleshooting without stopping PLC


Get a Quote