Product Description of ProSoft MVI69-S3964R
Description
Product Description of ProSoft MVI69-S3964R
MVI69-S3964R (Siemens 3964R Protocol Communication Module) is a dual-channel independent 3964R/RK512 serial communication module developed by ProSoft specifically for the Rockwell CompactLogix/MicroLogix platform. It provides 2 fully isolated RS-232/422 ports and supports the Siemens 3964R point-to-point protocol and RK512 communication, enabling high-speed and reliable data interconnection between Rockwell PLC and Siemens S5/S7 systems, as well as third-party 3964R devices. It is an industrial-grade standard solution for heterogeneous system integration. ProSoft Technology Inc.
I. Model Analysis
MVI69: Standard Series of CompactLogix 1769 Platform
S3964R: Siemens 3964R Protocol (including RK512)
Core Positioning: Dual Independent Serial Ports, Full Electrical Isolation, 3964R/RK512, Point-to-Point Communication, BCC Check, Large Capacity Data, Single Slot, Zero PLC Load
II. Core Hardware Specifications
Compatible Platforms
CompactLogix: L20/L23/L30/L31/L32/L35, L43/L45 (v16.03+)
MicroLogix: 1500 LRP
1769 I/O Bus, Single Slot Installation
Backplane Power Consumption: Maximum 800mA @ 5.1VDC
Serial Interfaces (3 Ports)
Application Ports (P1, P2): 2 Independent Paths, Jumper Options for RS-232/RS-422, RJ45 (with DB9 Adapter) ProSoft Technology Inc
RS-232: Supports Software Handshaking
RS-422: Full Duplex, Long Distance (1200m)
Configuration Port (CFG): 1 Path, Only RS-232, Used for Configuration / Debugging ProSoft Technology Inc
Electrical Isolation: 500Vrms Optical Isolation (Between Backplane and Serial Ports) ProSoft Technology Inc
Baud Rate: 110 ~ 115200 bps ProSoft Technology Inc
Data Format: 8 Data Bits, 1 Stop Bit, Even Check (3964R Standard)
Protocol Support
3964R: Siemens Standard Point-to-Point Protocol, BCC Check, Data Integrity Assurance
RK512: Supports Message Frames, Read/Write Services, Compatible with Siemens S5/S7 Communication ProSoft Technology Inc
Data Buffer: 4000 Bytes (2000 Bytes Read / 2000 Bytes Write) Bidirectional Shared Database ProSoft Technology Inc
Communication Capacity
Dual Port Independent Operation, Point-to-Point Peer-to-Peer Communication
Support for Sending / Receiving Messages, Data Block Read/Write, Status Monitoring ProSoft Technology Inc
LED Status: OK, BP, CFG, P1, P2, ERR Six Sets of Indicators
Operating Environment
Temperature: 0°C ~ +60°C
Storage: -40°C ~ +85°C
Humidity: 5% ~ 95% (No Condensation)
Certification: CE, UL, cURus, RoHS ProSoft Technology Inc
III. Core Functions and Performance
1. 3964R/RK512 Dual Protocol Communication (Core Advantage)
3964R Point-to-Point Protocol
Siemens Standard: Reliable, Point-to-Point, Bidirectional Data Exchange
BCC Block Check: Ensures 100% Data Integrity in Transmission
Automatic Redundancy, Timeout Handling, Link Monitoring: Industrial-grade Reliability ProSoft Technology Inc
Peer-to-Peer Communication: No Master/Slave Division, Both Parties Actively Send and Receive
RK512 Expansion Function
Support for Message Frames (MESSAGE), Read/Write Data Blocks ProSoft Technology Inc
Compatible with Siemens S5, S7 System's Standard Communication Services ProSoft Technology Inc Variable address mapping: Direct read and write to each other's data area. ProSoft Technology Inc.
Dual ports are completely independent.
Ports P1 and P2 do not interfere with each other and have independent configuration parameters and protocols.
Dual links in parallel: Connect two 3964R devices simultaneously.
RS-232/422 dual mode: Adapt to short-distance / long-distance, point-to-point / multi-point networking. ProSoft Technology Inc.
2. Seamless integration with PLC system
Deep integration with Studio 5000 / RSLogix
Provide AOI, UDT, example ladder diagram programs: No need for low-level programming
Module status, port status, data transmission, error codes are all mapped to PLC tags
Configuration files are saved to PLC project, and one-click backup / restoration are available. ProSoft Technology Inc. ProSoft Configuration Builder (PCB)
Visualization parameter configuration, message editing, data monitoring ProSoft Technology Inc
Online debugging, message capture, event logs, error diagnosis ProSoft Technology Inc
Configuration export/import, batch deployment, project cloning
3. Industrial-grade reliability
Full electrical isolation
500Vrms isolation: anti-surge, anti-static, eliminating ground circulation, protecting PLC and field devices ProSoft Technology Inc
Powerful diagnostics and fault tolerance
Automatic reconnection in case of disconnection, retry on timeout, error counting ProSoft Technology Inc
Detailed status codes, event logs, communication quality statistics ProSoft Technology Inc
Dual-port redundancy, hot backup of critical links ProSoft Technology Inc
Independent operation
Zero PLC CPU load,不影响 system scanning time
Module failure does not affect PLC host
Four. Core features and advantages
1. Professional 3964R communication
Compatible with Siemens original factory: 100% compatible with S5/S7 3964R/RK512 ProSoft Technology Inc
BCC verification + automatic retransmission: zero data loss
Dual independent ports: double connection capability, saving slots
500V full isolation: stable operation in extreme industrial environments ProSoft Technology Inc
2. Flexible, universal
RS-232/422 dual mode: short distance / long distance, point-to-point / multi-point full compatibility ProSoft Technology Inc
3964R/RK512 dual protocols: compatible with all Siemens 3964R devices ProSoft Technology Inc
Peer-to-peer communication: no master-slave restriction, flexible networking
Single slot, high integration: saving space, reducing cost
3. Easy to use, reliable
AOI/UDT out of the box ready: rapid development, reducing debugging
PCB visualization configuration: lowering technical threshold, improving efficiency ProSoft Technology Inc
Industrial-grade design, wide temperature range, no fan: long-term stability, maintenance-free
3-year warranty, global technical support: guarantee investment, trouble-free operation ProSoft Technology Inc
Five. Typical application scenarios
Rockwell ↔ Siemens interconnection: CompactLogix ↔ S5/S7 PLC 3964R high-speed data exchange ProSoft Technology Inc
Old plant system integration: S5 system integration into CompactLogix new system ProSoft Technology Inc
Point-to-point device communication: CompactLogix connects 3964R instruments, HMI, drivers
Dual-link redundancy: critical equipment dual 3964R links hot backup ProSoft Technology Inc
Long-distance communication: RS-422 full duplex, reliable transmission up to 1200m ProSoft Technology Inc
OEM equipment: dual-port parallel connection of two Siemens devices
Six. Summary
MVI69-S3964R is a professional-level solution for 3964R/RK512 communication on the CompactLogix platform. With dual independent fully isolated serial ports (RS-232/422), 3964R/RK512 dual protocols, BCC data verification, peer-to-peer point-to-point communication, 4000-word large-capacity database, zero PLC load, deep integration with Studio 5000, industrial-grade reliability as core advantages, specifically designed for Rockwell-Siemens system interconnection, upgrading of old factory S5, point-to-point device communication, long-distance reliable data exchange, and dual-link redundant design, it is a high-performance, highly reliable, one-stop industrial-grade standard module for Rockwell PLC to access Siemens 3964R network. ProSoft Technology Inc.
Get a Quote