TC-305-01-5M0
May 15, 2026

TC-305-01-5M0

The TC‑305‑01‑5M0 is a TMR field communication cable for the ICS Triplex Trusted T8000 safety system. It connects the T8151C Communication Interface Module to field termination or remote I/O modules, providing fault‑tolerant, triple‑channel communication for safety‑critical data. TC‑305‑01: PVC jacket, general‑purpose indoor/rack cable TC‑305‑02: LS0H (Low Smoke Zero Halogen) version 5M0: 5 meter standard length This cable is used for TMR safety communication links between the main controller’s communication module and the field devices in Trusted T8000 systems.

Description

ICS12.jpg

1. General Description

The TC‑305‑01‑5M0 is a TMR field communication cable for the ICS Triplex Trusted T8000 safety system. It connects the T8151C Communication Interface Module to field termination or remote I/O modules, providing fault‑tolerant, triple‑channel communication for safety‑critical data.
  • TC‑305‑01: PVC jacket, general‑purpose indoor/rack cable

  • TC‑305‑02: LS0H (Low Smoke Zero Halogen) version

  • 5M0: 5 meter standard length

This cable is used for TMR safety communication links between the main controller’s communication module and the field devices in Trusted T8000 systems.

2. Key Features

  • TMR triple‑channel fault‑tolerant communication

  • Connects: T8151C Comm Interface ↔ Field Termination / I/O

  • Length: 5 m; other options: 2M0, 10M0, 20M0

  • PVC outer jacket (TC‑305‑01) for cabinet/raceway installation

  • Individual pair shield + overall shield for high EMI/RFI immunity

  • Keyed, polarity‑protected connectors to prevent misconnection

  • Hot‑swap compatible (no system shutdown required)

  • SIL 3 / SIL 4 compliant (system level)

  • Flame retardant: IEC 60332‑1


3. Electrical Specifications

  • Architecture: TMR (3 × differential communication channels)

  • Conductor: 22 AWG stranded tinned copper

  • Insulation: PVC

  • Shielding: Foil + braid (≥95% coverage)

  • Rated voltage: 300 V

  • Operating voltage: 24 VDC (signal/power)

  • Dielectric withstand: 500 VDC

  • Data rate: Proprietary high‑speed TMR safety protocol

  • Current rating: 3 A max per power pair


4. Mechanical Specifications

  • Length: 5 m (16.4 ft)

  • Outer jacket: Black PVC

  • Outer diameter: Approx. 12 mm

  • Weight: Approx. 1.4 kg

  • Minimum bend radius: 10 × OD (≈120 mm)

  • Connectors:

    • T8151C end: D‑sub or proprietary multi‑pin connector

    • Field end: Pre‑terminated flying leads or customer‑specified connector


5. Environmental Specifications

  • Operating temperature: −40 °C to +70 °C

  • Storage temperature: −40 °C to +85 °C

  • Humidity: 5%–95% RH, non‑condensing

  • Pollution degree: PD2

  • Flame rating: IEC 60332‑1

  • Halogen content: Halogenated (PVC; see TC‑305‑02 for LS0H)


6. Safety & Approvals

  • Standard: IEC 61508

  • SIL rating: SIL 3 / SIL 4 (system)

  • Approvals: CE, UL, CSA, ATEX, IECEx, TÜV

  • Compliance: RoHS, REACH


7. Compatibility

Exclusive to Trusted T8000 system:
  • T8151C Communication Interface Module

  • Trusted T8100 Controller Chassis

  • Trusted T8200 Expander Chassis

  • TMR safety I/O modules and field termination units


8. Ordering Information

  • TC‑305‑01‑5M0: 5 m PVC TMR communication cable (T8151C ↔ field)

  • TC‑305‑01‑2M0: 2 m

  • TC‑305‑01‑10M0: 10 m

  • TC‑305‑01‑20M0: 20 m

  • TC‑305‑02‑xxx: LS0H (low smoke zero halogen) version


Get a Quote