T9833

The T9833 is a 16‑channel, TMR redundant, fully isolated analog input termination assembly designed for the AADvance T9000 Safety Instrumented System (SIS). It provides the electrical interface between 4–20 mA field transmitters and the T9433 analog input module, offering signal conditioning, surge protection, EMI filtering, and galvanic isolation. T9833 is the TMR (triple‑redundant) counterpart of T9831 (simplex) and T9832 (dual), intended for SIL 3 safety loops such as ESD, F&G, BMS, and critical process control, where maximum fault tolerance is required.

Description

ICS3.jpg

1. General Description

The T9833 is a 16‑channel, TMR redundant, fully isolated analog input termination assembly designed for the AADvance T9000 Safety Instrumented System (SIS). It provides the electrical interface between 4–20 mA field transmitters and the T9433 analog input module, offering signal conditioning, surge protection, EMI filtering, and galvanic isolation.
T9833 is the TMR (triple‑redundant) counterpart of T9831 (simplex) and T9832 (dual), intended for SIL 3 safety loops such as ESD, F&G, BMS, and critical process control, where maximum fault tolerance is required.

2. Key Features

  • 16 analog input channels, TMR triple modular redundancy

  • Fully isolated per channel (field‑to‑backplane, channel‑to‑channel)

  • Designed for direct use with T9433 (16‑Ch 4–20 mA Analog Input Module, TMR)

  • Accepts standard 4–20 mA DC transmitters (2‑wire / 4‑wire compatible)

  • Reinforced isolation: 1.5 kVDC field‑to‑backplane, 1 minute

  • Integrated TVS surge suppression and EMI/RFI low‑pass filtering per channel

  • Per‑channel diagnostics: open circuit, short circuit, overvoltage, ground fault

  • Hot‑swap compatible (online replacement without system shutdown)

  • Front‑panel LED status indicators for each channel (Run / Fault)

  • Conformal coated PCB for harsh industrial environments

  • Screw terminals for field wiring (16 AWG max)

  • SIL 3 certified per IEC 61508 (system level, TÜV)


3. Electrical Specifications

Input

  • Number of Channels: 16

  • Redundancy: TMR (Triple Modular Redundancy)

  • Signal Range: 4–20 mA DC

  • Input Impedance: 125 Ω per channel

  • Resolution: 16‑bit (matched to T9433)

  • Accuracy: ±0.05% FS (system level)

  • Transmitter Supply: 18–32 VDC (redundant from backplane)

Isolation

  • Field to Backplane: ±1.5 kVDC, 1 minute, reinforced

  • Channel to Channel: Isolated (no common ground)

Protection & Filtering

  • Surge Protection: TVS diode per channel (24 VDC rating)

  • EMI Filter: Low‑pass filter per channel (50/60 Hz rejection)

  • Fault Detection: Open / short / overvoltage / ground fault

Backplane Interface

  • Supply Voltage: 18–32 VDC (redundant)

  • Maximum Current: 450 mA

  • Power Dissipation: ≤ 6 W (20.5 BTU/h)


4. Mechanical Specifications

  • Form Factor: Single‑width 6U Termination Assembly (AADvance standard)

  • Dimensions (W × H): 132 mm × 126 mm (5.2 in × 5.0 in)

  • Weight: Approximately 360 g (13 oz)

  • Terminals: Screw‑type (field wiring)

  • Mounting: T9300 3‑Way I/O Base or T9100 System Chassis

  • Cooling: Conduction / natural convection (no fan required)


5. Environmental Specifications

  • Operating Temperature: −40 °C to +70 °C

  • Storage Temperature: −40 °C to +85 °C

  • Humidity: 5% to 95% RH, non‑condensing

  • Pollution Degree: PD2

  • Protection: Conformal coated PCB


6. Safety & Approvals

  • Safety Standard: IEC 61508

  • Safety Integrity Level: SIL 3 (system‑level TÜV certified)

  • Approvals: CE, UL, CSA, ATEX, IECEx, TÜV, CCC


7. Compatibility & Ordering Information

Compatible Modules

  • T9433: 16‑Channel 4–20 mA Analog Input Module (TMR)

  • T9300: 3‑Way I/O Base Unit

  • T9100: AADvance System Chassis

Ordering Codes

  • T9833: 16‑Ch Analog Input TA, TMR, Isolated

  • T9433: 16‑Ch 4–20 mA Analog Input Module, TMR

  • T9300: I/O Base, 3‑Way

  • T9100: Chassis, AADvance System


8. Typical Application

  • Emergency Shutdown (ESD) systems

  • Fire and Gas (F&G) detection systems

  • Burner Management Systems (BMS)

  • Critical process monitoring and control

  • SIL 3 safety instrumented loops requiring TMR fault tolerance


Get a Quote