T9832
May 15, 2026

T9832

T9832 is a 16‑channel, dual‑redundant, fully isolated analog input termination assembly for the AADvance T9000 safety system. It provides field wiring interface, signal conditioning, surge protection and galvanic isolation for 4–20 mA transmitters, working with T9432 16‑channel analog input module. T9832 is the dual‑redundant, isolated counterpart to T9831 (simplex) and T9833 (TMR), designed for fault‑tolerant analog signal acquisition in SIL 3 safety loops (ESD, F&G, BMS, critical process control).

Description

ICS13.jpg

1. Overview

T9832 is a 16‑channel, dual‑redundant, fully isolated analog input termination assembly for the AADvance T9000 safety system. It provides field wiring interface, signal conditioning, surge protection and galvanic isolation for 4–20 mA transmitters, working with T9432 16‑channel analog input module.
T9832 is the dual‑redundant, isolated counterpart to T9831 (simplex) and T9833 (TMR), designed for fault‑tolerant analog signal acquisition in SIL 3 safety loops (ESD, F&G, BMS, critical process control).

2. Key Features

  • 16 analog input channels, Dual redundant, fully isolated per channel

  • Dedicated for T9432 (16‑Ch 4–20 mA analog input module)

  • Accepts 4–20 mA field transmitters (2‑wire / 4‑wire)

  • Channel‑to‑channel & field‑to‑backplane isolation (reinforced)

  • Built‑in surge suppression (TVS diodes) and EMI/RFI filtering

  • Per‑channel fault detection: open circuit, short circuit, overvoltage, ground fault

  • Dual redundancy: single channel/module fault does not affect safety function

  • Screw terminals for easy field wiring (16 AWG max)

  • Conformal coated PCB for harsh industrial environments

  • Hot‑swap compatible (online replacement without system shutdown)

  • LED status indicators per channel (front‑panel visible)


3. Electrical Specifications

Input

  • Channels: 16, dual redundant, fully isolated

  • Signal range: 4–20 mA DC

  • Input impedance: 125 Ω (per channel)

  • Resolution: Matches T9432 (16‑bit)

  • Accuracy: ±0.05% FS (system level)

  • Transmitter supply: 18–32 VDC (from backplane, redundant)

Isolation

  • Field‑to‑backplane: ±1.5 kVDC, 1 minute, reinforced

  • Channel‑to‑channel: Isolated (no common ground)

Protection & Filtering

  • Surge protection: TVS diode per channel (24 VDC)

  • EMI filter: Low‑pass filter per channel (50 Hz/60 Hz rejection)

  • Fault detection: Open/short/overvoltage/ground fault

Backplane Interface

  • Supply: 18–32 VDC (redundant)

  • Max current: 450 mA

  • Power dissipation: ≤ 6 W (20.5 BTU/h)


4. Mechanical

  • Form factor: Single‑width 6U TA (AADvance standard)

  • Dimensions: 132 mm × 126 mm (5¼ in × 5 in)

  • Weight: ~360 g (13 oz)

  • Terminals: Screw‑type (field wiring)

  • Mounting: T9300 I/O base (3‑way) or T9100 chassis

  • Fuse access: Front‑panel (if equipped)


5. Environmental

  • Operating temperature: −40 °C to +70 °C

  • Storage temperature: −40 °C to +85 °C

  • Humidity: 5–95 % RH, non‑condensing

  • Pollution degree: PD2

  • Protection: Conformal coated


6. Safety & Approvals

  • IEC 61508 SIL 3 (system‑level, TÜV certified)

  • Approvals: CE, UL, CSA, ATEX, IECEx, TÜV, CCC


7. Compatibility & Ordering

Compatible Modules

  • T9432: 16‑Ch 4–20 mA Analog Input Module (Dual)

Ordering Information

  • T9832: 16‑Ch Analog Input TA, Dual, Isolated

  • T9432: 16‑Ch 4–20 mA Analog Input Module

  • T9300: 3‑Way I/O Base Unit

  • T9100: AADvance System Chassis


Get a Quote