T9110
May 15, 2026

T9110

The T9110 is the central TMR safety processor for the AADvance T9000 SIS platform. It executes safety application logic, manages all T9xxx I/O modules, provides redundant network communication, and performs continuous self‑diagnostics for SIL 3 safety integrity in ESD, BMS, and process shutdown systems.

Description

ICS5 - 副本.jpg

1. Introduction

The T9110 is the central TMR safety processor for the AADvance T9000 SIS platform. It executes safety application logic, manages all T9xxx I/O modules, provides redundant network communication, and performs continuous self‑diagnostics for SIL 3 safety integrity in ESD, BMS, and process shutdown systems.
T9110 operates as a triple‑modular redundant (TMR) controller with three synchronized processing slices, using TriVote™ majority voting to ensure single‑fault tolerance and fail‑safe behavior. It is the core of any AADvance safety system, paired with T9100 chassis, T9xxx I/O, and T98xx FTAs.
  • Function: TMR safety processor, logic execution, I/O control, network & diagnostics

  • Architecture: 3‑2‑0 TMR (three processing slices, majority vote)

  • Safety: IEC 61508 SIL 3 (TÜV), CE, UL, CSA, ATEX, IECEx

  • Processor: Triple 32‑bit RISC / ARM Cortex‑A9 (per slice)

  • Memory: 2 GB RAM / 8 GB Flash (high‑integrity, ECC)

  • Communication: Dual Ethernet (10/100 Mbps), RS‑232/485, Modbus TCP/RTU, EtherNet/IP

  • Redundancy: Hot‑swap, redundant power, redundant network

  • Operating Temp: –40 °C to +70 °C (conformal coated standard)


2. Product Overview

The T9110 is a single‑width, 6U TMR processor module for AADvance T9100 chassis, designed as the safety brain for critical process applications. It runs the AADvance Safety Kernel, executes user safety logic (ladder/function block), scans I/O, and communicates with HMI/SCADA and peer controllers.
Key features:
  • TMR 3‑2‑0 fault tolerance: Three independent processing slices execute the same logic; outputs voted 2‑of‑3 → single‑slice faults safe, no trip on single fault.

  • ECC memory & safe data: Error‑correcting RAM/Flash prevents data corruption; safe firmware & application storage.

  • Comprehensive diagnostics: BIST, watchdog, slice sync check, I/O communication health, network redundancy monitoring.

  • Hot‑swap: Online replacement without system shutdown or safety loop interruption.

  • Redundant communications: Dual Ethernet ports for network redundancy (switchover <100 ms).

  • SIL 3 certified: Meets IEC 61508 SIL 3 for process safety, ESD, BMS, and critical interlocks.

Common applications:
  • Emergency Shutdown (ESD) systems (oil & gas, refining)

  • Burner Management Systems (BMS) (power, chemical)

  • Turbine overspeed & protection (steam/gas turbines)

  • Critical process interlocks & safety trips

  • Fire & gas (F&G) suppression control

image

3. Specifications

3.1 Mechanical

  • Form Factor: T9100 chassis single‑width module, 6U

  • Dimensions (H × W × D): 266 mm × 31 mm × 220 mm

  • Weight: Approx. 1.1 kg

  • Mounting: AADvance T9100 chassis slots 1–12 (processor slot recommended: slot 1/2)

  • Protection: Conformal coated (standard T9110)

  • Enclosure Rating: IP20 (for cabinet installation)

3.2 Electrical

  • System Supply: 18–30 VDC (nominal 24 VDC ±10 %), dual redundant inputs

  • Power Consumption: ≤ 12 W (typical); ≤ 15 W (max, all ports active)

  • Backplane Isolation: 2500 VDC (processor ↔ I/O chassis)

  • Communication Port Isolation: 1500 VAC (Ethernet/serial ↔ system)

3.3 Processing & Memory

  • Architecture: Triple‑modular redundant (TMR), 3 synchronized slices

  • Processor per Slice: 32‑bit RISC / ARM Cortex‑A9

  • RAM: 2 GB DDRII, ECC protected

  • Flash: 8 GB, safe firmware & application storage

  • Real‑Time Clock (RTC): Battery‑backed, with diagnostics

  • Logic Execution: Ladder diagram, function block (IEC 61131‑3)

  • Scan Time: ≤ 1 ms (typical medium logic)

3.4 Communication Interfaces

  • Ethernet: 2 × 10/100 Mbps (RJ45), redundant, Modbus TCP, EtherNet/IP

  • Serial: 1 × RS‑232 / RS‑485 (configurable), Modbus RTU

  • Backplane: T9100 high‑speed I/O bus (TMR‑safe)

  • Redundancy: Dual Ethernet, automatic failover <100 ms

3.5 Functional & Safety

  • Redundancy: TMR 3‑2‑0, single‑fault safe

  • Voting: TriVote™ majority vote (2‑of‑3)

  • Diagnostics:

    • Power supply monitoring (over/undervoltage)

    • Processor slice sync & health check

    • ECC memory error detection & correction

    • Watchdog (per slice + system)

    • I/O communication health

    • Network redundancy & link status

  • Safe State: All outputs de‑energized on critical fault/power loss

  • PFHd: < 2.5 × 10⁻⁹ / hour (SIL 3)

3.6 Environmental

  • Operating Temperature: –40 °C to +70 °C

  • Storage Temperature: –40 °C to +85 °C

  • Humidity: 5–95 % RH, non‑condensing

  • Vibration: 10–57 Hz ±0.10 mm; 57–150 Hz 1.5 g

  • Shock: 20 g, ½ sine wave, 11 ms

  • Hazardous Area: ATEX / IECEx Ex ia IIC T4 Ga (with barriers)

3.7 Certifications

  • Safety: IEC 61508 SIL 3 (TÜV)

  • Approvals: CE, UL, CSA, ATEX, IECEx, FM


4. Front Panel Indicators

  • PWR (Green): ON = module power healthy; FLASHING = power fault

  • RUN (Green): ON = executing safety logic; FLASHING = init/BIST

  • FAULT (Red): ON = critical fault; FLASHING = minor fault

  • COM (Green): FLASHING = backplane I/O communication active

  • NET1 / NET2 (Yellow): FLASHING = Ethernet link/activity; ON = link up


5. Installation

  • Chassis: Insert into T9100 chassis vacant slot (prefer slot 1/2 for processor)

  • Hot‑Swap: Supported (T9100 SmartSlot)

  • Front‑Panel Screws: Torque 0.8–1.0 Nm

  • Cabling: Route Ethernet/serial cables away from high‑power AC (EMI avoidance)

  • Environmental Note: Standard T9110 is conformal coated for harsh environments


6. Wiring & Communication

  • Ethernet: NET1/NET2 to redundant switches (Modbus TCP/EtherNet/IP)

  • Serial: RS‑232/485 to HMI/SCADA or Modbus RTU devices

  • Backplane: Auto‑connects to T9100 I/O bus (no user wiring)

  • Power: Dual 24 VDC inputs (redundant) to T9100 chassis


7. Ordering Information

  • T9110: AADvance TMR Safety Processor Module (–40 °C to +70 °C, coated)

  • T9100: AADvance system chassis (6U, 12 slots)

  • T9100‑F2: Dual‑channel TMR safety relay output module

  • T9850: Safety relay FTA (for T9100‑F2)


Get a Quote