T8448C
May 15, 2026

T8448C

The T8448C is a conformal coated, triple‑modular redundant (TMR) 32‑channel DC output module with zone interface for the Trusted T8000 Safety Instrumented System (SIS). It is the harsh‑environment version of T8448, with full conformal coating to resist moisture, dust, chemical contaminants, and condensation in extreme industrial and hazardous (Ex) areas. Designed for safety‑critical ESD, process shutdown, and burner management, it provides 3‑2‑0 TMR fault tolerance, intrinsically safe (Ex ia) 24 VDC field interface, and comprehensive per‑channel diagnostics, suitable for petrochemical, offshore, power, and mining applications.

Description

ICS5.jpg

1. Introduction

The T8448C is a conformal coated, triple‑modular redundant (TMR) 32‑channel DC output module with zone interface for the Trusted T8000 Safety Instrumented System (SIS). It is the harsh‑environment version of T8448, with full conformal coating to resist moisture, dust, chemical contaminants, and condensation in extreme industrial and hazardous (Ex) areas.
Designed for safety‑critical ESD, process shutdown, and burner management, it provides 3‑2‑0 TMR fault tolerance, intrinsically safe (Ex ia) 24 VDC field interface, and comprehensive per‑channel diagnostics, suitable for petrochemical, offshore, power, and mining applications.
  • Function: 32‑channel TMR DC output + hazardous area zone interface (Ex ia)

  • Outputs: 32 × 24 VDC discrete outputs (8 power groups × 4 channels)

  • Field Supply: 18–32 VDC (nominal 24 VDC)

  • Load: Solenoids, valves, relays, contactors

  • Safety: IEC 61508 SIL 3 (TÜV), ATEX / IECEx Ex ia IIC T4 Ga

  • Architecture: 3‑2‑0 TMR, HIFT, TriVote™ fault correction

  • Isolation: 2500 VDC opto‑galvanic (field ↔ system; ch ↔ ch)

  • SOE: 1 ms time‑stamp resolution

  • Hot‑swap: Supported (Companion Slot / SmartSlot)

  • Coating: Conformal coated (acrylic) for harsh environments


2. Product Overview

The T8448C is a single‑width, 6U TMR output module for T8100 / T8400 chassis, optimized for high humidity, corrosive, dusty, or wide‑temperature hazardous locations. It integrates 32 independent DC output channels arranged into 8 electrically isolated power groups (4 channels per group), enabling flexible safety load partitioning.
Key features (differences from standard T8448):
  • Conformal coated PCB and components (acrylic resin)

  • Extended operating temperature: –40 °C to +70 °C

  • Enhanced resistance to moisture, salt mist, dust, and chemical vapors

  • Same TMR core, I/O performance, and safety certification as T8448

Common features with T8448:
  • 32 × TMR DC outputs (24 VDC, 2 A per channel)

  • 8 independent power groups (4 ch/group; 8 A max per group)

  • Intrinsically safe (Ex ia) zone interface for hazardous locations

  • 2500 VDC channel‑to‑channel and system isolation

  • Per‑channel diagnostics: open/short circuit, overload, mismatch

  • TMR voting with single‑fault correction (TriVote™)

  • Hot‑swap & hot‑standby (companion slot)

  • 1 ms SOE logging for all output events & faults


3. Specifications

3.1 Mechanical

  • Form Factor: T8000 chassis single‑width module, 6U height

  • Dimensions (H × W × D): 266 mm × 31 mm × 303 mm

  • Weight: Approx. 1.2–1.3 kg

  • Mounting: T8100 / T8400 chassis slots 1–16

  • Termination: T8848 FTA (Zone Interface / Ex FTA)

  • Protection: Conformal coated (acrylic) PCB and components

3.2 Electrical

  • System Supply: 20–32 VDC (nominal 24 VDC)

  • Power Consumption: ≤ 25 W

  • Field Supply (Outputs): 18–32 VDC (nominal 24 VDC)

  • Output Channels: 32, grouped into 8 × 4‑channel power groups

  • Output Rating: 2 A continuous per channel; 8 A peak surge

  • Group Rating: 8 A max per power group

  • Isolation: 2500 VDC opto‑galvanic (field ↔ system; ch ↔ ch)

  • Leakage Current: < 100 µA (off‑state)

  • On‑State Voltage Drop: ≤ 1.2 VDC @ 2 A

3.3 Functional

  • Redundancy: TMR (3 slices, 3‑2‑0 fault tolerance)

  • Voting: TriVote™; auto‑corrects single‑slice faults

  • Diagnostics:

    • Open/short circuit detection (per channel)

    • Overload / overcurrent protection (per group)

    • TMR mismatch & drift monitoring

    • Output voltage/current health check

    • On‑board BIST (periodic self‑test)

  • SOE Resolution: 1 ms (output state changes, faults, trips)

  • Response Time: ≤ 1 ms (command to output)

  • Fault Tolerance: Single‑channel/group fault does not affect safety function

3.4 Environmental (Enhanced for Harsh Conditions)

  • Operating Temperature: –40 °C to +70 °C (vs 0 °C to +60 °C for T8448)

  • Storage Temperature: –40 °C to +85 °C

  • Humidity: 5–95 % RH, non‑condensing (coating reduces condensation risk)

  • Vibration: 10–57 Hz ±0.075 mm; 57–150 Hz 1.0 g

  • Shock: 15 g, ½ sine wave, 11 ms

  • Hazardous Area: ATEX / IECEx Ex ia IIC T4 Ga

  • Chemical Resistance: Resists salt mist, oil vapors, and common industrial gases

3.5 Safety & Certification

  • Safety Standard: IEC 61508 SIL 3 (TÜV Certified)

  • Approvals: CE, UL, CSA, ATEX, IECEx, FM

  • Fault Tolerance: TMR 3‑2‑0; single‑fault safe

  • PFHd: < 1.0 × 10⁻⁹ / hour (SIL 3)


4. Front Panel Indicators

  • PWR (Green): ON = module power healthy

  • RUN (Green): ON = active; FLASHING = BIST/initialization

  • FAULT (Red): ON = critical fault; FLASHING = minor fault

  • COM (Green): FLASHING = backplane communication active

  • CH1–CH32 LEDs: Per‑channel status (ON = energized; FLASH = fault)


5. Installation

  • Chassis: Insert into any vacant slot in T8100 / T8400 chassis

  • Hot‑Swap: Supported (Companion Slot / SmartSlot)

  • Front‑Panel Screws: Torque 0.8–1.0 Nm

  • Termination: Connect to T8848 Ex FTA for hazardous area field wiring

  • Environmental Note: T8448C is preferred for sites with > 85 % RH, corrosive vapors, or temperature extremes


6. Wiring

  • Output Channels: To solenoids, valves, relays (24 VDC, 2 A max)

  • Field Power: 18–32 VDC to T8848 FTA (per power group)

  • Isolation: Field side isolated 2500 VDC from system/backplane

  • Wire Gauge: 16–22 AWG, stranded, with suitable insulation for Ex areas


7. Ordering Information

  • T8448: Standard 32‑channel TMR DC output module (0 °C to +60 °C)

  • T8448C: Conformal coated 32‑channel TMR DC output module (–40 °C to +70 °C, harsh environments)

  • T8848: Dedicated Ex zone interface FTA for T8448 / T8448C

  • T8100 / T8400: Trusted system chassis


Get a Quote