T8424C
May 15, 2026

T8424C

The T8424C is a 40‑channel 120 VAC digital input module with Triple Modular Redundancy (TMR) and per‑channel 1oo2D voting, designed for the Trusted T8000 Safety Instrumented System (SIS). It is the conformal coated (acrylic) wide‑temperature version of the standard T8424, intended for harsh industrial environments where moisture, dust, vibration, or corrosive gases are present.

Description

ICS1.jpg

1. Introduction

The T8424C is a 40‑channel 120 VAC digital input module with Triple Modular Redundancy (TMR) and per‑channel 1oo2D voting, designed for the Trusted T8000 Safety Instrumented System (SIS).
It is the conformal coated (acrylic) wide‑temperature version of the standard T8424, intended for harsh industrial environments where moisture, dust, vibration, or corrosive gases are present.
  • Function: Monitors 120 VAC discrete field devices (switches, contactors, relay contacts)

  • Architecture: Fully triplicated TMR (3‑2‑0) + per‑channel 1oo2D hardware voting

  • Safety Certification: IEC 61508 SIL 3 / SIL 4

  • Coating: Acrylic conformal coating (T8424C only)

  • Operating Temperature: –40 °C to +70 °C (T8424: 0 °C to +60 °C)

  • Channels: 40 × 120 VAC digital inputs

  • Isolation: 2500 VDC optical isolation (channel‑to‑channel, channel‑to‑system)

  • SOE Resolution: 1 ms

  • Hot‑Swap: Supported


2. Product Overview

The T8424C is a compact, high‑density input module for the Trusted T8000 SIS platform. It provides 40 independent 120 VAC digital input channels with full TMR fault tolerance and advanced diagnostics.
Key features include:
  • 40 channels of isolated 120 VAC digital input

  • Triple modular redundancy (TMR) for fault‑tolerant operation

  • Per‑channel 1oo2D voting for fault detection and isolation

  • Sigma‑delta ADCs for precise voltage measurement

  • 2500 VDC optical isolation between field and backplane

  • Onboard SOE (Sequence of Events) logging with 1 ms resolution

  • Per‑channel open/short circuit detection

  • Conformal coating for harsh environments (T8424C)

  • Wide operating temperature range: –40 °C to +70 °C

  • Front‑panel LED status indicators

  • Hot‑swap capable for online replacement

  • Compatible with T8100 / T8400 Trusted controller chassis


3. Specifications

3.1 Mechanical

  • Form Factor: T8000 chassis module, 56 mm wide, 6U height

  • Dimensions (H × W × D): 255 mm × 56 mm × 210 mm

  • Weight: 1.3 kg (2.87 lbs)

  • Mounting: T8100 / T8400 chassis slots 1–16

  • Connectors: Front‑panel terminal blocks TB1–TB5 (8 channels each)

  • PCB Protection: Acrylic conformal coating (T8424C)

3.2 Electrical

  • System Supply: 20–32 VDC (nominal 24 VDC)

  • Power Consumption: ≤ 5 W

  • Input Channels: 40 × 120 VAC digital inputs

  • Input Voltage Thresholds:

    • Logic 1: 90–150 VAC

    • Logic 0: < 30 VAC

  • Input Current: Approximately 4 mA per channel at 120 VAC

  • Input Type: Sink (NPN) / Source (PNP) configurable

  • Isolation: 2500 VDC optical barrier

  • Backplane Interface: Trusted Backplane Bus (TBB), TMR

3.3 Functional

  • Voting: 1oo2D per channel (triple measurement + comparison)

  • SOE Resolution: 1 ms per channel state change

  • Diagnostics:

    • Open‑circuit detection (per channel, with line resistor)

    • Short‑circuit detection (per channel)

    • Onboard BIST (Built‑In Self‑Test)

    • Fault logging to system HMI

  • Response Time: ≤ 2.0 ms channel‑to‑backplane

  • Data Integrity: BER < 10⁻¹²

3.4 Environmental (T8424C Rated)

  • Operating Temperature: –40 °C to +70 °C

  • Storage Temperature: –40 °C to +85 °C

  • Humidity: 5–95 % RH, non‑condensing

  • Altitude: ≤ 2000 m

  • Vibration: IEC 60068‑2‑6 (1 g, 10–150 Hz)

  • Shock: IEC 60068‑2‑27 (15 g, 11 ms)

3.5 Safety & Certification

  • Safety Standard: IEC 61508 SIL 3 / SIL 4

  • Certifications: CE, UL, CSA, ATEX II 3G Ex ec IIC T4 Gc, IECEx

  • Fault Tolerance: TMR (3‑2‑0), 1oo2D per channel

  • PFHd: < 8.0 × 10⁻¹⁰ / hour (SIL 4)


4. Front Panel Indicators

  • PWR (Green): ON = module power healthy; OFF = no power

  • RUN (Green): ON = module active; FLASHING = initialization / BIST

  • FAULT (Red): ON = critical fault; FLASHING = minor fault

  • COM (Green): FLASHING = backplane communication active

  • TB1–TB5: Terminal blocks for 40 input channels

  • FG: Functional ground (chassis earth)


5. Installation

  • Chassis: Insert into any vacant slot in T8100 or T8400 Trusted chassis

  • Hot‑Swap: Supported; no system shutdown required

  • Mounting Torque: 0.8–1.0 Nm for front‑panel screws

  • Orientation: Ensure correct alignment with backplane connectors


6. Wiring

  • Terminal Blocks: TB1–TB5 (8 channels each)

  • Field Wiring:

    • Connect 120 VAC line (L) to group common terminal

    • Connect field device output to channel input terminal

    • Connect device common to 120 VAC neutral (N)

  • Wire Gauge: 16–22 AWG stranded

  • Terminal Torque: 0.5–0.6 Nm

  • Line Resistor: 10 kΩ per channel for open‑circuit monitoring


7. Operation

  • Power‑Up: PWR ON; RUN flashes during BIST (5–10 seconds)

  • Normal Operation: PWR and RUN steady green; FAULT OFF; COM flashing

  • Fault Conditions:

    • FAULT ON: critical fault (short circuit, TMR mismatch)

    • FAULT FLASHING: minor fault (single‑lane mismatch)

  • SOE Logging: All state changes time‑stamped at 1 ms resolution


8. Ordering Information

  • T8424: Standard 40‑Ch 120 VAC DI (0 °C to +60 °C)

  • T8424C: Conformal coated, –40 °C to +70 °C

  • TC‑8424: Terminal block cable kit

  • T8100 / T8400: Trusted controller chassis


Get a Quote