T3464
May 14, 2026

T3464

The T3464 is a 16‑channel AC guarded digital output module from Rockwell ICS Regent series, designed for safety‑critical industrial applications. It provides fault‑tolerant switching of 110 VAC to field loads, ensuring no single fault causes unintended output activation. It integrates with Regent/Trusted TMR (Triple Modular Redundancy) systems for high‑reliability process control and safety interlocks.

Description

T3464.jpg

T3464(3.jpg

T3464(2.jpg

The T3464 is a 16‑channel AC guarded digital output module from Rockwell ICS Regent series, designed for safety‑critical industrial applications. It provides fault‑tolerant switching of 110 VAC to field loads, ensuring no single fault causes unintended output activation. It integrates with Regent/Trusted TMR (Triple Modular Redundancy) systems for high‑reliability process control and safety interlocks.

2. Key Features

  • 16 guarded AC outputs, grouped as two isolated banks of 8 channels each.

  • Fault‑tolerant parallel operation: Dual modules can work in parallel for uninterrupted load control.

  • Hot‑swappable: Online replacement without system shutdown.

  • 100% self‑diagnostics: Comprehensive fault detection with LED and display indicators.

  • Front‑panel accessible fuses: Simplifies maintenance.

  • 2500 Vrms isolation: Between field and logic circuits for EMI protection.

  • TÜV certified (Risk Class 5): Compliant with IEC 61508 for safety integrity.

3. Technical Specifications

  • Model: T3464

  • Manufacturer: Rockwell ICS Triplex

  • System Compatibility: Regent/Trusted T3 series TMR systems

  • Input Voltage: 24 VDC ±10% (logic power)

  • Output Voltage: 110 VAC (user‑supplied field power)

  • Output Current: 4 A per channel; 32 A total

  • Isolation Voltage: 2500 Vrms (field‑to‑logic)

  • Power Consumption: 3 W (max)

  • Operating Temperature: −40°C to +70°C

  • Storage Temperature: −40°C to +85°C

  • Humidity: 5%–95% non‑condensing

  • Dimensions: 120 mm × 140 mm × 30 mm

  • Weight: 0.5 kg

  • Certifications: TÜV (Risk Class 5), CE, UL

4. Installation & Wiring

4.1 Mechanical Installation

  • Mount in a standard ICS Triplex T3 series rack (slots 0–15).

  • Ensure chassis grounding for ESD protection.

  • Maintain ≥25 mm clearance around the module for ventilation.

4.2 Wiring

  • Backplane Connector: Connects to system backplane for 24 VDC logic power and I/O Safetybus communication.

  • Field Terminals:

    • Two 110 VAC power inputs (for 8‑channel banks).

    • 16 output channels (CH1–CH16) for field loads (valves, relays, contactors).

  • Cable Requirements: 16–20 AWG stranded copper wire; torque terminals to 0.8–1.0 N·m.

  • Fuses: Install 5 A fuses per bank (front‑panel accessible).

5. Operation

5.1 Power‑Up & Self‑Test

  • Apply 24 VDC logic power; the module runs a 5‑second initialization sequence:

    1. Display test (8.8.8.8)

    2. RAM/PROM self‑tests

    3. Normal mode (blinking decimal points indicate processor activity)

  • “PWR” LED (green) lights; “FAULT” LED (red) remains off if healthy.

5.2 Normal Operation

  • Output Control: Triplicated commands from the system processor are voted by two independent microcontroller sections; outputs activate only if both sections agree.

  • LED Indicators:

    • Green: Channel ON.

    • Off: Channel OFF.

    • Red: Channel fault (overload/short circuit).

  • Display: Shows channel status and diagnostic codes (e.g., “AFO” for RAM failure).

5.3 Fault Handling

  • Channel Fault: Module disables the faulty channel; “FAULT” LED lights. Check wiring, load, or fuses.

  • Module Fault: Communication loss or internal error. Verify backplane connection or replace the module (hot‑swap supported).

6. Maintenance

  • Monthly Inspection: Check LED status, wiring tightness, and fuse condition.

  • Cleaning: Use a dry cloth to remove dust; avoid harsh chemicals.

  • Self‑Test: Trigger via system software quarterly to validate diagnostics.

  • Replacement: Hot‑swap procedure: remove faulty module, insert new one, and confirm operation via system diagnostics.

7. Safety Precautions

  • ESD Protection: Wear a grounded wrist strap when handling the module.

  • Power Isolation: Disconnect both 24 VDC logic power and 110 VAC field power before wiring.

  • Load Ratings: Do not exceed 4 A per channel or 32 A total current.

  • Fault Response: Address “FAULT” LED alerts immediately to maintain safety integrity.


Get a Quote