3122A-403-4-00
Description




1. Model Code Definition
2. Core Electrical Parameters
Rated Output Power: 22 kW
Input Voltage: 3-phase AC 200~240 V (Nominal 230 V)
Input Frequency: 50 Hz / 60 Hz
Rated Output Current: 85 A
Output Voltage Range: 0 ~ 230 V three-phase AC
Output Frequency Range: 0 ~ 400 Hz
Control Mode: V/F open-loop control
Overload Capacity: 150% rated current for 60 seconds, 125% long-term operation
Switching Frequency: 2~16 kHz adjustable
Full-load Power Factor: ≥0.95
Operational Efficiency: ≥97%
3. Physical & Environmental Specifications
Protection Class: IP20
Cooling Mode: Built-in high-efficiency fan forced air cooling
Operating Ambient Temperature: 0 °C ~ +45 °C
Storage Temperature: -25 °C ~ +70 °C
Working Humidity: 5%~95%, non-condensing environment
Installation Method: Vertical wall-mounted installation
Maximum Applicable Altitude: ≤1000m without power derating
Vibration Resistance: Adapt to ordinary industrial vibration environment
4. Built-in Control Interfaces
Standard onboard RS485 communication interface, support Modbus RTU protocol
0-10V DC analog speed regulation input terminal
Multi-group programmable 24V DC digital input terminals
Programmable relay signal output terminals
PTC motor over-temperature protection access interface
External dynamic braking resistor matching interface
Multi-section fixed speed control terminals
5. Main Operating Functions
Acceleration and deceleration time adjustable freely within 0.1~600 seconds
Integrated dynamic braking and DC braking function for fast stop
Intelligent energy-saving operation mode, automatically optimize light-load operation
Three control modes: local panel operation, external terminal control, remote communication control
Speed slip compensation function to improve load operation speed stability
Soft start and soft stop function to reduce mechanical impact and starting current
Built-in PID constant pressure and constant speed automatic control function
Support parameter copying, saving and restoring functions
6. Complete Safety Protection System
Instantaneous overcurrent and thermal overload protection
Overvoltage and undervoltage protection
Three-phase input phase loss detection protection
Inverter internal module over-temperature protection
Electronic thermal motor overload protection
Output terminal short circuit protection
Motor side ground fault protection
Running stall prevention protection
Control terminal anti-static and reverse connection protection
7. Installation & Wiring Specifications
Cut off the total power supply before all wiring and maintenance operations
Power main circuit cables and control signal cables must be laid separately to avoid electromagnetic interference
The equipment PE grounding terminal must be reliably connected to the factory general grounding wire
Reserve sufficient ventilation and heat dissipation space around the inverter, keep upper and lower gaps
It is forbidden to install in dusty, humid, oil mist and strong corrosive gas sites
It is recommended to use shielded special motor cables for connecting motors to reduce frequency conversion interference
8. Standard Commissioning Steps
Carefully check all wiring to eliminate wrong wiring and hidden short circuit risks
Confirm that the on-site input power voltage is consistent with the inverter rated voltage
Set basic motor parameters: rated voltage, rated current, rated frequency and rated speed
Select the corresponding operation control mode according to actual production requirements
Complete acceleration and deceleration time, upper and lower limit frequency setting
First perform no-load trial operation to check motor running direction and running sound
After confirming stable no-load operation, gradually load and put into formal production operation
9. Daily Maintenance & Inspection Guidelines
Regularly clean cooling fan and internal accumulated dust every 3-6 months
Periodically check whether all power terminals and control terminals are loose
Real-time monitor operating current and internal operating temperature during operation
Replace aging and abnormal noise cooling fans in time
Professional certified electricians must be arranged for equipment fault inspection and maintenance