4409
Description

TRICONEX 4409
Safety Manager Module (SMM) – TMR System Management & Safety Lifecycle
Tricon SIS – SIL3 – Datasheet Specification (English)
1. General
Model: 4409
Type: Safety Manager Module (SMM)
System: Tricon TMR SIS (v10 / v11)
Safety Level: SIL3 (IEC 61508 / IEC 61511)
Architecture: Triple Modular Redundancy (TMR), 2oo3 voting
Certification: TUV Rheinland, FM, CSA, ATEX/IECEx, UL, CE
Hot‑swap: Yes
Form factor: Full‑height Tricon module
Function: Centralized safety system management, lifecycle tracking, configuration control, compliance reporting, and TMR health supervision
2. Hardware Specifications
Processor: TMR triple‑core 32‑bit safety management CPU
Memory:
128 MB SDRAM
256 MB Flash (firmware, logs, safety records)
Backplane interface: Tricon TMR backplane, 33 MHz
Power consumption: ≤ 20 W (max)
Real‑time clock (RTC): Battery‑backed, 1 ms resolution
3. Key Functions
TMR system health monitoring & voting control
Safety lifecycle management (SIL3 compliance)
Configuration version control & audit trail
SOE (Sequence of Events) logging, 1 ms resolution
Fault diagnostics & predictive maintenance alerts
Redundancy management (hot spare, fault recovery)
Safety parameter storage & integrity check
4. Communication Interfaces
2 × UCN (Universal Communication Network) ports, isolated
Data rate: 10 Mbps
Isolation: 500 VDC
1 × 10/100 Mbps Ethernet (RJ45, for config/reporting)
1 × RS‑232 (local maintenance)
Protocols: Modbus TCP, TriStation 1131, OPC UA (optional)
5. TMR & Safety Features
Voting: 2oo3 TMR on all safety logic & data
Fault coverage: ≥ 99%
Diagnostics:
TMR mismatch & channel fault
Over‑temperature / over‑voltage
Configuration corruption
Battery low / RTC fault
Communication link failure
Data integrity: 32‑bit CRC + TMR cross‑compare
Safety record retention: ≥ 10 years (non‑volatile)
6. Electrical
Backplane voltage: 18–30 VDC
Isolation:
UCN ports: 500 VDC
Ethernet/serial: 1500 VAC
Battery: 3.6 V lithium, replaceable, ≥ 5 years life
7. Environmental
Operating temperature: –40°C to +70°C
Storage temperature: –40°C to +85°C
Humidity: 5%–95%, non‑condensing
Vibration: 5–200 Hz, 2 g (IEC 60068‑2‑6)
Protection: Conformal coated, IP20
8. Mechanical
Dimensions (W×H×D): 178 × 127 × 63 mm
Weight: ≈ 1.0 kg
9. Front Panel LEDs
PWR (Green): Power OK
RUN (Green): TMR normal operation
FAULT (Red): Module/TMR/safety fault
LOW BATT (Yellow): Battery low
SPARE RDY (Green): Hot spare ready
UCN A / UCN B (Yellow): UCN port active
XMIT (Yellow): Data transmitting
10. Compatibility
Chassis: Tricon full‑height slots (v10/v11)
Software: TriStation 1131 v4.0+
Replacement for: Legacy 4400 system management functions
11. Approvals
SIL3 (IEC 61508)
TUV Rheinland, FM, CSA
ATEX/IECEx (Zone 2)
UL, CE
Get a Quote