4200
May 18, 2026

4200

TRICONEX 4200 TMR Enhanced Communication Module

Description

4200.jpg

4200(3.jpg

4200(2.jpg

TRICONEX 4200

TMR Enhanced Communication Module

Tricon SIS – SIL3 – Datasheet Specification (English)

1. General

  • Model: 4200

  • Type: TMR Enhanced Communication Module

  • System: Tricon TMR SIS (v10 / v11)

  • Safety Level: SIL3 (IEC 61508 / IEC 61511)

  • Architecture: Triple Modular Redundancy (TMR), 2oo3 voting

  • Certification: TUV, FM, CSA, ATEX / IECEx

  • Hot-swap: Yes

  • Max per chassis: 4 modules

  • Form factor: Full-height Tricon module

2. Communication Interfaces

  • 2 × 10/100 Mbps Ethernet (RJ45)

    • Redundant, auto-sensing, IEEE 802.3 compliant

  • 2 × Isolated Serial Ports

    • Software selectable: RS‑232 / RS‑422 / RS‑485

    • Isolation: 1500 V AC (channel-to-backplane)

  • 1 × Isolated Parallel Port (Centronics)

3. Protocols Supported

  • Modbus TCP (Master/Slave)

  • Modbus RTU/ASCII (Master/Slave)

  • TriStation 1131

  • DNP3, OPC (via gateway)

  • TCP/IP, UDP, ARP, ICMP

4. Ethernet Specifications

  • Data rate: 10 / 100 Mbps, full/half duplex

  • Cable: CAT5e, up to 100 m

  • Redundancy: Dual-port, fault-tolerant

  • Modbus TCP: Up to 64 concurrent connections

5. Serial Specifications

  • Baud rates: 1200 ~ 115.2 kbps

  • RS‑485: 1 master, up to 32 slaves, 1200 m

  • Isolation: 1500 V AC

6. Safety & Diagnostics

  • Voting: 2oo3 TMR on all communication data

  • Fault coverage: ≥ 99%

  • Diagnostics:

    Link loss, CRC error, parity/framing error, TMR mismatch, duplicate IP, port fault

  • SOE resolution: ≤ 1 ms

7. Electrical

  • Backplane power: 5 VDC, 24 VDC

  • Power consumption: ≤ 15 W

  • Data integrity: 32‑bit CRC + TMR cross‑channel comparison

8. Environmental

  • Operating temperature: –40°C to +70°C

  • Storage temperature: –40°C to +85°C

  • Humidity: 5%–95%, non‑condensing

  • Vibration: 5–200 Hz, 2 g

  • Protection: Conformal coated

9. Mechanical

  • Dimensions: 178 × 127 × 63 mm

  • Weight: ≈ 0.9 kg

10. Front Panel LEDs

  • PWR (Green): Power OK

  • RUN (Green): TMR normal operation

  • FAULT (Red): Module / link / TMR fault

  • LAN1 / LAN2 (Yellow/Green): Ethernet activity / link

  • CH0 / CH1 (Yellow): Serial TX/RX activity

11. Compatibility

  • Chassis: Tricon full‑height slots (v10/v11)

  • Software: TriStation 1131 v4.0+

  • Processors: Tricon MP v10 / v11

  • Replacement for: 4118 (Ethernet) + 4119 (Serial)


Get a Quote