3725
Description

TRICONEX 3725
16‑Channel 24VDC TMR Digital Output Module (SIL3)
English Specification (No Images)
1. General Description
2. Basic Information
Model: 3725
Type: 16‑Channel Digital Output (TMR)
Output: 24VDC, 2A max per channel
System Compatibility: Tricon V9 / V10 / V11
Safety Level: SIL3 (IEC 61508 / IEC 61511)
Certifications: TUV, FM, CSA, ATEX/IECEx
Architecture: TMR, 2oo3 voting
Status: In production & supported
3. Key Features
16 output channels, 24VDC / 2A (sink/source configurable)
TMR fault tolerance, 2oo3 voting logic
Fast response time: <3ms
Fail‑safe de‑energize on fault
Channel‑to‑ground isolation: 1,500VDC
Diagnostics: open load, short circuit, overcurrent, TMR mismatch
Hot‑swappable; online replacement
Overload protection: electronic current limiting
LED status per channel
4. Technical Parameters
4.1 Digital Output
Voltage: 24VDC nominal (18–30VDC range)
Current: 2A max per channel, 8A max per module
Channels: 16, isolated, sink/source configurable
Response time: <3ms
On‑state resistance: <0.5Ω
Off‑state leakage: <100μA
4.2 Safety & Isolation
Voting: 2‑out‑of‑3 (2oo3)
Fault coverage: ≥99%
Isolation: 1,500VDC (channel–ground)
Diagnostics: open load, short circuit, overcurrent, TMR mismatch
4.3 Environmental
Operating temp: –40°C to +70°C
Storage temp: –40°C to +85°C
Humidity: 5%–95%, non‑condensing
Vibration: 5–200Hz, 2G
4.4 Power & Mechanical
Backplane: 5VDC
Power consumption: ≤18W
Dimensions: 178 × 127 × 63mm
Weight: ~0.8kg
5. Function
6. LED Indicators
PWR (Green): Power OK
RUN (Green): Normal operation
FAULT (Red): Module/channel fault
CH0–CH15 (Yellow): Channel active
7. Installation & Configuration
Insert into Tricon I/O slots
Wire 24VDC field devices to terminal base
Configure sink/source and diagnostics via TriStation 1131
Verify LEDs and output status
8. Typical Applications
ESD emergency shutdown valves (24VDC solenoids)
Fire & gas suppression system triggers
Critical pump/trip valve interlocks
Alarm beacons, horns, and annunciators
Oil/gas, chemical, power plant safety instrumentation
9. Maintenance
Hot swap faulty modules online
Inspect wiring/terminals annually
Test solenoid/valve loads periodically
Review fault/SOE logs
10. Compatibility
Terminal base: 3725TB series
Software: TriStation 1131
Compatible processors: 3008, 3005 series
Get a Quote