TRICONEX 3624 is a supervised digital output (SDO) module with triple modular redundancy (TMR), designed for Tricon V9/V10/V11 SIS safety systems. It provides 16-channel isolated 24VDC solid-state output with comprehensive load/field diagnostics, meeting SIL3 (IEC 61508). Widely used in ESD, BMS, and safety interlock loops.

Description

3624.jpg

3624(3.jpg

3624(2.jpg

TRICONEX 3624

16 Channel 24VDC TMR Supervised Digital Output Module

English Specification (No Images)

1. General Description

TRICONEX 3624 is a supervised digital output (SDO) module with triple modular redundancy (TMR), designed for Tricon V9/V10/V11 SIS safety systems. It provides 16-channel isolated 24VDC solid-state output with comprehensive load/field diagnostics, meeting SIL3 (IEC 61508). Widely used in ESD, BMS, and safety interlock loops.

2. Basic Information

  • Model: 3624

  • Type: 16CH 24VDC TMR Supervised Digital Output (SDO)

  • Applicable System: Tricon V9 / V10 / V11

  • Safety Grade: SIL3 (IEC 61508, IEC 61511)

  • Certifications: TUV, FM, CSA, ATEX

  • Architecture: Triple Modular Redundancy (TMR), 2oo3 voting

  • Supply Status: In production & maintenance supported

3. Key Features

  • 16 supervised outputs (common group), 24VDC, source/sink selectable via terminal board (3624T=source, 3624R=sink)

  • TMR 2oo3 fault tolerance; diagnostics coverage ≥99%

  • Per-channel supervision: open load, short circuit, overcurrent, field power loss detection

  • Solid-state output; self-protected (OV/OC/OT), no external fuses required

  • Hot-swappable; online replacement without system shutdown

  • 1500VDC channel-to-ground isolation; high noise immunity

  • Configurable fail-safe state via TriStation 1131

4. Technical Parameters

4.1 Electrical

  • Rated voltage: 24VDC

  • Operating range: 16–30VDC (max 36VDC transient)

  • Per-channel continuous current: 0.7A

  • Per-channel surge current: 4.8A (10ms max)

  • Min load current: 30mA (for supervision)

  • Off-state leakage: ≤4mA

  • On-state voltage drop: <1.5VDC

  • Response time: <10ms (logic to output)

  • Isolation: 1500VDC minimum (channel-to-ground)

4.2 Safety & Diagnosis

  • Voting: 2-out-of-3 (2oo3)

  • Fault coverage: ≥99%

  • Diagnostics: open load, short (<5Ω), overcurrent, field power loss, module health

  • Indicators: PWR, RUN, FAULT; per-channel CH status

4.3 Environmental

  • Operating temp: 0°C to +60°C

  • Storage temp: -40°C to +85°C

  • Humidity: 5%–95%, non-condensing

  • Vibration: 5–200Hz, 2G

4.4 Power

  • Backplane: 5VDC

  • Module power: ≤10W

5. Function

Receives safety logic commands from the main controller; drives 24VDC devices (solenoid valves, safety relays, alarms). Provides real-time supervision of output switches, wiring, and loads; reports faults to the system; supports SOE for precise action time logging.

6. LED Definition

  • PWR (Green): Power OK

  • RUN (Green): Normal operation, communication OK

  • FAULT (Red): Module/channel fault

  • CH (Yellow): Channel active

  • LOAD (Yellow): Load fault (open/missing)

  • POWER (Yellow): Field power fault

7. Installation & Configuration

  1. Insert into Tricon I/O slots 4–11

  2. Wire 24VDC loads to matched terminal board (3624T/3624R)

  3. Configure logic/diagnostics via TriStation 1131

  4. Verify LEDs after power-up

8. Typical Applications

  • ESD emergency shutdown solenoid valve control

  • BMS burner safety actuator outputs

  • Fire & gas system alarm/shutdown control

  • Power/chemical plant safety interlocks

  • All SIL3 process safety loops

9. Maintenance

  • Hot swap faulty modules online

  • Regularly check wiring/terminals

  • Review system fault & SOE logs

  • Compatible with main controllers: 3008, 3005 series

10. Compatibility

  • Terminal base: 3624T (source) / 3624R (sink)

  • Software: TriStation 1131

  • Compatible processors: 3008, 3005 series


Get a Quote