3008
Description



TRICONEX 3008
Main Processor Module (TMR, SIL3, Legacy Tricon SIS)
Official English Specification (consistent format: 3005/3006/3009)
1. General Description
2. Model Information
Model: 3008
Type: Main Processor Module (TMR Controller)
System Series: Legacy Tricon SIS (not Trident/3006)
Safety Level: SIL3 (IEC 61508, TÜV/FM/CSA)
Part Number: 3008‑010 / 7400120‑400
Status: Legacy / End‑of‑Support (EoS) (replaced by 3005/3006)
3. Main Features
TMR Architecture: 3× independent 32‑bit CPUs, 2oo3 voting, fault‑tolerant
Legacy Platform: Original Tricon SIS (1990s–2000s)
Memory: 16MB DRAM / 32KB battery‑backed SRAM / 6MB Flash PROM
Scan Time: ≤10ms (typical safety logic)
I/O Capacity: Up to 8,000 points (mixed AI/DI/AO/DO)
TriBus: 25Mbps high‑speed backplane, 32‑bit CRC protected
Serial Comm: Isolated RS‑232 (500VDC isolation) for diagnostics
SOE: 1ms resolution (basic logging)
Hot‑Swappable: Online replacement; redundant CPU support
4. Technical Parameters
4.1 Processing
CPU: 3× Motorola MPC860, 32‑bit, 50MHz
Memory: 16MB DRAM / 32KB SRAM (battery) / 6MB Flash
Scan Time: ≤10ms
I/O Capacity: Up to 8,000 points
Voting: 2oo3 fault‑tolerant, mid‑value selection
4.2 Communication Interfaces
TriBus: 25Mbps backplane, 32‑bit CRC, fully isolated
Serial: 1× RS‑232 (25‑pin), 500VDC isolation
Protocol Support: TriBus, Modbus RTU (serial)
Ethernet: None (no onboard Ethernet; requires comm module)
4.3 Redundancy & Safety
Diagnostic Coverage: >99%
System Availability: 99.999%
Safety Certification: SIL3 (IEC 61508), TÜV, FM, CSA
4.4 Environmental
Operating Temperature: 0°C to +60°C
Storage Temperature: −40°C to +85°C
Humidity: 5%–95% non‑condensing
Vibration: 5–200Hz, 1g
Protection: IP20
4.5 Power & Physical
Backplane Power: 5VDC
Power Consumption: ≤15W
Dimensions: Legacy Tricon full‑size (228×160×75mm)
Weight: ~1.5kg
5. Function Overview
System Control: Executes safety logic, manages legacy Tricon I/O, coordinates TMR voting
TriBus Gateway: High‑speed I/O communication (no Ethernet)
Data Logging: Basic 1ms SOE (limited storage)
Redundancy Management: Seamless TMR failover; no single point of failure
Online Maintenance: Logic download, hot‑swap, runtime diagnostics
6. LED Indicators
PASS (Green): Self‑diagnostics OK
ACTIVE (Green): Program executing
FAULT (Red): CPU/memory/comm fault or voting mismatch
MAINT1/MAINT2 (Yellow): Maintenance alerts
7. Installation & Configuration
Insert 3008 into legacy Tricon full‑size CPU slot
Connect RS‑232 to diagnostic terminal
Use TriStation 1131 (v3.x) to program logic, configure TriBus
Verify: PASS+ACTIVE green; no FAULT red
8. Typical Applications
Legacy ESD/BMS: Oil/gas, chemical, power (old plants)
Small‑to‑Medium SIS: Up to 8,000 I/O points
Retrofit Projects: Replaced by 3005 (Trident) or 3006 (next‑gen)
9. Maintenance & Support
EoS Status: No official support; third‑party repair only
Hot‑swap 3008 with spare (legacy stock)
Review fault logs via TriStation v3.x
Upgrade path: Migrate to 3005 (Trident) or 3006 (3008/3009 SIS)
10. Compatibility
Compatible Systems: Legacy Tricon SIS (not Trident/3006)
Configuration Software: TriStation 1131 (v3.x only)
Matching I/O: Legacy Tricon series (e.g., 2700/2750)
Model: 3008
Description: Legacy TMR Main Processor Module, SIL3, End‑of‑Support
Get a Quote