3005
Description

TRICONEX 3005
Enhanced Main Processor Module (EMP II, TMR, SIL3)
Official English Specification (consistent format: 2651/2652/2658/2700/2750/2755/3002/3003)
1. General Description
2. Model Information
Model: 3005 (EMP II)
Type: Enhanced Main Processor Module (TMR Controller)
System Series: Tricon Tricon / Trident SIS
Safety Level: SIL3 (IEC 61508)
Certification: TÜV, FM, CSA, ATEX, IECEx
Part Number: 3005‑010 / 7400120‑500
Status: Active / In production
3. Main Features
TMR Architecture: 3× independent 32‑bit CPUs, 2oo3 voting, fault‑tolerant
Enhanced Performance: Faster scan, expanded memory, up to 12,000 I/O points
Large Memory: 256MB RAM / 2GB Flash
Multi‑Protocol Comm: TriBus, Ethernet (Modbus TCP), Serial (RS‑232/485)
SOE: 1ms resolution sequence‑of‑events logging
Online Changes: Download logic without shutdown
Hot‑Swappable: Replace CPU online; redundant CPU support
Full Diagnostics: CPU, memory, I/O, comm, and power health monitoring
4. Technical Parameters
4.1 Processing
CPU: 3× 32‑bit Motorola MPC860 (or higher), 400MHz
Memory: 256MB RAM / 2GB Flash
Scan Time: ≤5ms (typical safety logic)
I/O Capacity: Up to 12,000 points (mixed AI/DI/AO/DO)
Voting: 2oo3 fault‑tolerant, mid‑value selection
4.2 Communication Interfaces
TriBus: TMR backplane bus (high‑speed I/O)
Ethernet: 2× 10/100Mbps (Modbus TCP, P2P)
Serial: 2× RS‑232/485 (Modbus RTU, ASCII)
Protocol Support: Modbus TCP/RTU, Tricon P2P, OPC UA
Isolation: 1500Vrms (comm vs backplane)
4.3 Redundancy & Safety
Diagnostic Coverage: >99%
System Availability: 99.999%
Safety Certification: SIL3 (IEC 61508), TÜV, FM, CSA
4.4 Environmental
Operating Temperature: −20°C to +60°C
Storage Temperature: −40°C to +85°C
Humidity: 5%–95% non‑condensing
Vibration: 5–200Hz, 1g
Protection: IP20
4.5 Power & Physical
Backplane Power: 5VDC
Power Consumption: ≤20W
Dimensions: Standard Tricon full‑size (150×130×35mm)
Weight: ~1.2kg
5. Function Overview
System Control: Executes safety logic, manages all I/O (2700/2755/3002/3003), coordinates TMR voting
Communication Gateway: Connects SIS to DCS/SCADA via Ethernet/serial
Data Logging: SOE (1ms) and historical data for compliance
Redundancy Management: Seamless failover between TMR channels; no single point of failure
Online Maintenance: Logic download, hot‑swap, and runtime diagnostics
6. LED Indicators
PWR (Green): 5VDC backplane power OK
RUN (Green): Module active, TMR sync normal
FAULT (Red): CPU/memory/comm fault or voting mismatch
COM (Yellow): Ethernet/serial activity
I/O (Yellow): I/O module communication status
7. Installation & Configuration
Insert 3005 into Tricon/Trident full‑size CPU slot
Connect Ethernet/serial cables to front‑panel ports
Use TriStation 1131 (v4.0+) to program logic, configure comm, enable SOE
Verify: PWR+RUN green; no FAULT red; COM/I/O LEDs reflect activity
8. Typical Applications
ESD: Emergency shutdown logic, pressure/temp/level safety loops
BMS: Burner management, flame safety, fuel gas valve control
FGS: Fire/gas detection, deluge system control
Turbine: Speed/temp/pressure monitoring, trip logic
Large‑Scale SIS: Up to 12,000 I/O for complex plants
9. Maintenance
Hot‑swap faulty 3005 without downtime
Check Ethernet/serial connections
Review fault logs/SOE via TriStation
Redundant CPU (3005) for fault tolerance
10. Compatibility
Compatible Systems: Tricon Tricon, Trident SIS
Configuration Software: TriStation 1131 (v4.0+)
Matching I/O: 2700 (DI), 2755 (AI), 3002 (DO/PI), 3003 (Comm)
Model: 3005 (EMP II)
Description: Enhanced TMR Main Processor Module, SIL3
Get a Quote