2750
Description

TRICONEX 2750
Programmable Control Module (TMR, SIL3)
Official English Specification Manual (consistent format with 2651/2652/2658/2700)
1. General Description
2. Model Information
Model: 2750
Type: Programmable Control Module (TMR CPU)
System Series: Triconex Tricon / Trident SIS
Safety Level: SIL3 (IEC 61508)
Certification: TÜV, FM, CSA
Part Number: 3000105‑010
Status: Active / In production
3. Main Features
Triple Modular Redundancy (TMR): 3 independent processors, 2oo3 voting
User Programmable: Supports C‑language & IEC 61131‑3 (TriStation 1131)
Large I/O Capacity: Max 256 inputs / 128 outputs (digital+analog)
Multi‑Protocol Communication: Modbus RTU/TCP, Ethernet, RS‑232, RS‑485
Deterministic Execution: Fixed scan rate (1–10ms) for safety logic
Full Diagnostics: Self‑test, fault isolation, voting mismatch alarm
SOE Timing: 1ms resolution sequence‑of‑events logging
Hot‑Swappable: Online replacement without shutdown
4. Technical Parameters
4.1 CPU & Performance
Architecture: 3× 32‑bit RISC processors (TMR)
Execution Rate: 1ms–10ms configurable scan
Memory: 8MB program / 8MB data (redundant)
Programming: C‑language, LD/FBD/ST (TriStation 1131)
4.2 I/O Capacity
Digital Inputs: 256 max (24VDC)
Digital Outputs: 128 max (24VDC/relay)
Analog Inputs: 64 max (4–20mA / 0–10V)
Analog Outputs: 32 max (4–20mA / 0–10V)
4.3 Communication
Ports: 2× Ethernet, 2× RS‑485, 1× RS‑232
Protocols: Modbus TCP/RTU, Tricon Peer‑to‑Peer
Speed: Ethernet 10/100Mbps; RS‑485 115.2kbps
4.4 Redundancy & Safety
Architecture: TMR (3‑channel independent)
Voting: 2oo3 fault‑tolerant
Diagnostic Coverage: >99%
System Availability: 99.999%
4.5 Environmental
Operating Temperature: −20°C to +60°C
Storage Temperature: −40°C to +85°C
Relative Humidity: 5%–95% non‑condensing
Vibration: 5–200Hz, 1g
4.6 Power & Physical
Backplane Power: 5VDC / 3.3VDC
Power Consumption: ≤25W
Dimensions: 197mm × 287mm × 170mm
Weight: ~4.5kg
5. Function Overview
Executes SIL3 safety logic for ESD, BMS, FGS, and interlocks
Processes up to 256 inputs / 128 outputs (digital+analog)
Performs 2oo3 voting on all internal logic and I/O data
Communicates with DCS, HMI, and other SIS nodes via multi‑protocol ports
Logs SOE with 1ms resolution for incident analysis
Supports redundant 2750 pairs for high‑availability systems
6. LED Indicators
PWR (Green): 5VDC backplane power OK
RUN (Green): Module active, TMR sync normal
FAULT (Red): CPU/voting/I/O fault
COMM (Yellow): Network activity
FORCE (White): I/O forced state active
7. Installation & Configuration
Insert 2750 into Trident baseplate CPU slot
Connect Ethernet/serial cables to front‑panel ports
Use TriStation 1131 to:
Download safety logic (C or IEC 61131‑3)
Configure I/O mapping & communication
Set scan rate (1–10ms) & fault thresholds
Verify: PWR+RUN green; no FAULT red; COMM flashes on traffic
8. Typical Applications
ESD Emergency Shutdown Systems (oil & gas, petrochemical)
BMS Burner Management Systems (power, refining)
FGS Fire & Gas Systems (process plants)
Turbine/Generator Safety Controllers (power)
SIL3 Safety Interlock Controllers (chemical, pharmaceutical)
9. Maintenance
Hot‑swap faulty 2750 without downtime
Check Ethernet/serial cables and port LEDs
Review fault logs & SOE via TriStation
Keep firmware updated for latest diagnostics
10. Compatibility
Compatible Systems: Triconex Tricon, Trident SIS
Configuration Software: TriStation 1131 (v4.0+)
Matching I/O Modules: 2700 (DI), 2701 (DO), 2751 (AI), 2752 (AO)
Model: 2750
Description: TMR Programmable Control Module, SIL3, 256In/128Out, Multi‑Protocol
Get a Quote