2652
Description



TRICONEX 2652
Single Channel AC Digital Output Module TMR SIL3
Official English Specification Manual
1. General Description
2. Model Information
Model: 2652
Type: Single Channel AC Digital Output Module
System Series: Trident Triconex
Safety Level: SIL3 compliant IEC61508
Certification: TUV, FM, CSA
3. Main Features
Single isolated AC output channel, 115VAC standard voltage
Complete TMR three-circuit independent control, 2oo3 hardware voting
Built-in over current, short circuit and overload protection
Full diagnosis: open load, short circuit, voltage abnormal detection
Support online hot swap, no system stop during replacement
High anti-interference design, suitable for harsh industrial site
Fail-safe output mode configurable via software
4. Technical Parameters
4.1 Output Specification
Rated working voltage: 115VAC
Working voltage range: 90~132VAC, 50/60Hz
Continuous output current: 2A
Instant surge current: max 5A
Output switch type: solid state relay output
Response time: ≤15ms
Isolation strength: 2500Vrms channel to backplane
4.2 Redundancy & Safety
Control structure: Triple Modular Redundancy TMR
Voting mode: 2 out of 3 voting
Fault diagnosis coverage: above 99%
System availability: 99.999%
4.3 Environment Parameter
Operating temperature: 0℃ ~ +60℃
Storage temperature: -40℃ ~ +85℃
Relative humidity: 5%~95% non-condensing
Vibration resistance: 5~200Hz 1G
4.4 Power Consumption
Backplane power supply: 5VDC
Module power consumption: ≤12W
4.5 Physical Size
Standard Trident module size
Installed on system baseplate, 19-inch cabinet compatible
5. Function Introduction
Receive safety logic command from main processor module
Three independent circuits execute output action simultaneously
Automatically judge fault state and report fault information
Support SOE sequence of events timestamp recording
Real-time upload working status to TriStation configuration software
6. LED Status Indication
PWR Green light: module power supply normal
RUN Green light: module running normally and communicating
FAULT Red light: module or channel fault alarm
CH Yellow light: current channel output status
7. Installation and Configuration
Insert 2652 module into empty slot of Trident system baseplate
Connect 115VAC field load equipment to module terminal base
Use TriStation 1131 software to set output logic and fail-safe state
Open channel diagnosis function, set fault alarm threshold
Confirm all indicator lights are in normal state after power on
8. Typical Application
ESD emergency shutdown system AC solenoid valve control
BMS burner management system AC executing mechanism
Field 115VAC safety relay and alarm equipment drive
Power plant safety interlock AC control loop
Fire and gas protection system executive unit output
9. Daily Maintenance
Realize non-stop hot swap replacement of faulty module
Regularly check field AC wiring and terminal connection tightness
View system fault log and SOE event record regularly
Match with Trident main module 2101 for normal use
10. Matching Equipment
Compatible main module: 2101
Applicable system: Trident SIS system
Configuration software: TriStation 1131
Matching terminal base: dedicated AC output terminal base