2651
Description

TRICONEX 2651
Digital Output Module (1‑Channel, TMR, 115 VAC, 2 A, SIL 3)
Official Specification & User Manual (English)
1. General Description
2. Part Number & Type
Model: 2651
Type: Digital Output Module (DO), TMR
Series: Trident (Triconex / Schneider Electric)
Safety Level: SIL 3 (IEC 61508)
Approvals: TÜV Rheinland, FM, CSA
Status: Obsolete / Discontinued
3. Key Features
1 Isolated Digital Output Channel
115 VAC nominal (90–132 VAC operating).
Triple Modular Redundancy (TMR)
2oo3 voting; three independent output circuits.
High Switching Capacity
2 A continuous, 5 A surge per channel.
2500 V RMS Isolation
Channel‑to‑backplane galvanic isolation.
Comprehensive Diagnostics
Load open/short, overcurrent, overvoltage, backplane fault.
Hot‑Swappable
Replace online without system shutdown.
SIL 3 Fault Coverage
99% diagnostic coverage.
4. Technical Specifications
4.1 Output Channel
Number: 1 channel, isolated
Signal Type: 115 VAC (90–132 VAC, 50/60 Hz)
Continuous Current: 2 A @ 115 VAC
Surge Current: 5 A (1 sec max)
Switching Speed: ≤ 15 ms
Isolation: 2500 V RMS (channel‑to‑backplane)
4.2 Safety & Redundancy
Architecture: TMR, 2oo3 voting
Safety Integrity Level: SIL 3
Fault Coverage: > 99%
System Availability: 99.999%
4.3 Environmental
Operating Temperature: 0°C to +60°C
Storage Temperature: −40°C to +85°C
Humidity: 5%–95% non‑condensing
Vibration: 5–200 Hz, 1g
4.4 Power
Backplane: 5 VDC / 1.5 A
Power Consumption: ≤ 12 W
4.5 Physical
Dimensions: 133 mm × 114 mm × 32 mm (5.25” × 4.50” × 1.25”)
Weight: ~0.45 kg
Mounting: Trident baseplate, 19” rack
5. Functional Overview
TMR Output Switching
Three independent solid‑state relays; 2oo3 voted output.
Overload Protection
Electronic current limiting, short‑circuit protection.
Diagnostics & Alarms
Open load, short circuit, overcurrent, overvoltage, module overtemperature; reported via TriStation.
SOE Logging
Time‑stamps state changes (≤ 40 ms).
6. LED Indicators
PWR (Green): Module power OK
RUN (Green): Active, communicating
FAULT (Red): Channel/module fault
CH 1 (Yellow): Output ON/OFF status
7. Installation & Configuration
Insert 2651 into an empty Trident baseplate slot.
Connect 115 VAC field devices (solenoids, contactors) to the DO terminal base.
Use TriStation 1131 to:
Set output logic (NO/NC)
Enable diagnostics (open/short, overcurrent)
Configure pulse mode (if required)
Verify: PWR + RUN green, no FAULT red.
8. Typical Applications
ESD solenoid valves (115 VAC)
Fire & gas suppression system actuators
115 VAC motor contactors (small loads)
SIL 3 safety interlocks in oil & gas, power, chemical
Critical alarm annunciators
9. Maintenance
Hot‑swap faulty 2651 without shutdown.
Inspect field wiring and terminal base connections.
Review fault/SOE logs via TriStation.
Note: 2651 is obsolete; replacement: 2402 (24 VDC) or 2652 (115 VAC).
10. Ordering Information
Model: 2651
Description: Triconex Trident 1‑Channel TMR Digital Output Module (115 VAC, 2 A, SIL 3)
Compatible with: Trident Chassis, 2101/3700A MP Modules, TriStation 1131
Replacement: 2652 (115 VAC, TMR, 2 A)
Get a Quote