2402
May 18, 2026

2402

The TRICONEX 2402 is a 16‑channel digital output (DO) baseplate for the Triconex Trident Safety Instrumented System (SIS). It works with standard Trident DO modules to provide triple‑modular redundant (TMR) on/off control for 24–125 VDC loads in safety‑critical applications up to SIL 3, targeting oil & gas, petrochemical, power, and process industries. The 2402 is a current‑limited, high‑isolation baseplate that distributes field power and provides voltage loopback diagnostics for each channel.

Description

2402.jpg

2402(3.jpg

2402(2.jpg

TRICONEX 2402

Digital Output Baseplate (16‑Channel, TMR, 24–125 VDC)

Official Specification & User Manual (English)

1. General Description

The TRICONEX 2402 is a 16‑channel digital output (DO) baseplate for the Triconex Trident Safety Instrumented System (SIS). It works with standard Trident DO modules to provide triple‑modular redundant (TMR) on/off control for 24–125 VDC loads in safety‑critical applications up to SIL 3, targeting oil & gas, petrochemical, power, and process industries.
The 2402 is a current‑limited, high‑isolation baseplate that distributes field power and provides voltage loopback diagnostics for each channel.

2. Part Number & Type

  • Model: 2402

  • Type: Digital Output Baseplate (DO), TMR

  • Series: Trident (Triconex / Schneider Electric)

  • Safety Level: SIL 3 (IEC 61508)

  • Approvals: TÜV Rheinland, FM, CSA

3. Key Features

  • 16 Isolated Digital Output Channels

    Supports 24–125 VDC field devices (solenoids, relays, alarms).

  • Triple Modular Redundancy (TMR)

    2oo3 voting; three independent output paths per channel.

  • High Voltage Isolation

    2500 V RMS channel‑to‑backplane isolation.

  • Per‑Channel Current Limiting

    Protects against short circuits and overloads.

  • Voltage Loopback Diagnostics

    Detects open load, missing field power, and wiring faults.

  • Hot‑Swappable

    Replace upper DO module online without shutdown.

  • Dual Field Power Inputs

    PS1 / PS2 for redundant 24–125 VDC field power.

4. Technical Specifications

4.1 Output Channels

  • Number: 16 channels, isolated

  • Signal Type: 24–125 VDC digital output

  • Current Limit: 1.5 A max per channel

  • Response Time: ≤ 10 ms

4.2 Safety & Redundancy

  • Architecture: TMR, 2oo3 voting

  • Safety Integrity Level: SIL 3

  • Fault Coverage: > 99%

4.3 Environmental

  • Operating Temperature: 0°C to +60°C

  • Storage Temperature: −40°C to +85°C

  • Humidity: 5%–95% non‑condensing

  • Vibration: 5–200 Hz, 1g

4.4 Power

  • Backplane: 5 VDC / 1.0 A

  • Field Power: 24–125 VDC (PS1 / PS2, user‑supplied)

4.5 Physical

  • Dimensions: 178 mm × 249 mm × 32 mm (7.0” × 9.79” × 1.25”)

  • Weight: ~0.5 kg

  • Mounting: Trident baseplate, 19” rack

5. Functional Overview

  • Field Power Distribution

    Distributes redundant 24–125 VDC (PS1/PS2) to 16 channels.

  • TMR Output Drive

    Works with DO module to provide 2oo3‑voted on/off commands.

  • Diagnostics & Alarms

    Voltage loopback checks detect open load, short circuit, missing field power; reported via TriStation.

  • SOE Logging

    Time‑stamps state changes and faults (≤ 40 ms).

6. LED Indicators (on mating DO module)

  • PWR (Green): Module power OK

  • RUN (Green): Active, communicating

  • FAULT (Red): Channel/module fault

  • CH 1–16 (Yellow): Channel ON

7. Installation & Configuration

  1. Mount 2402 in Trident chassis slot.

  2. Plug compatible DO module (e.g., 2401) onto 2402.

  3. Connect 24–125 VDC field power to PS1/PS2 terminals.

  4. Wire field devices (solenoids, relays) to 16‑channel terminal block.

  5. Use TriStation 1131 to:

    • Set fail‑safe state

    • Enable voltage loopback diagnostics

    • Configure fault thresholds

  6. Verify: PWR + RUN green, no FAULT red.

8. Typical Applications

  • ESD solenoid valves (24–125 VDC)

  • BMS fuel shutoff valves

  • Safety relay coils

  • Fire & gas alarm beacons/horns

  • HIPPS auxiliary relays

9. Maintenance

  • Hot‑swap DO module; baseplate is non‑swappable.

  • Inspect PS1/PS2 field power and wiring.

  • Review SOE and fault logs via TriStation.

10. Ordering Information

  • Model: 2402

  • Description: Triconex Trident 16‑Channel TMR Digital Output Baseplate (24–125 VDC)

  • Compatible with: 2401 DO Module, Trident Chassis, TriStation 1131


Get a Quote