FTA-544
Description
I. Core Explanation (FTA = Field Terminal Assembly)
FTA‑544 is not an I/O module, but a field terminal adapter board:
It is inserted behind the Tricon AO module to convert the backplane signals into isolated analog outputs that can be wired on-site, with fuses, surge protection, and LED status indicators.
II. Specification Parameters (Official Consistent Version)
1. Channels and Signals
Channels: 4 analog output channels (AO), isolated type
Signal range (software selectable): 4–20mA (default), 0–20mA, 0–5V, 0–10V
Resolution: 16bit
Accuracy: ±0.05% FS
Response time: ≤100ms
Isolation: Channel-to-channel isolation, channel-to-backplane isolation 1500VAC
2. Electrical
Power supply: 24VDC (±10%), supplied by the backplane or external power source
Load capacity:
Current output: ≤800Ω (24V power supply)
Voltage output: ≥10kΩ
Protection: Replaceable fuses per channel, surge suppression, polarity reversal protection, overload self-recovery
Power consumption: Approximately 5W
3. Mechanical and Environmental
Size: 225 × 112 × 40mm
Weight: Approximately 0.84kg
Installation: Tricon I/O rack slot, installed in pairs with the AO module
Temperature: -40℃ ~ +70℃
Certifications: CE, UL, CSA, TUV SIL3 (overall certification for the supporting module)
4. Panel and Wiring Interface:
Inside: D‑Sub 37 connector, connects to Tricon AO module
Outside: Screw terminal block, for on-site 4–20mA/0–10V wiring
Indicators (per channel):
PWR (green): Power supply on the terminal board is normal
CH1–CH4 (yellow): Channel output activated / fault
FAULT (red): Fuse blown / overload / open circuit
III. Compatible Modules (Required Pair)
FTA‑544 specifically for Tricon 4-channel isolated AO module:
AO3401: 4-channel 4–20mA/0–10V, isolated, SIL3 (most commonly used)
AO2401: 4-channel, point-to-point isolated, high stability
IV. Typical Applications
ESD/SIS: Control valve opening, actuator position, frequency converter setpoint
Process: Pressure / Flow / Level regulating valve analog control
Unit: Anti-surge valve, guide vane opening, governor setpoint
Safety: SIL3 loop analog output, with open circuit / short circuit diagnosis
V. Quick Reference for the Same Series (To Avoid Confusion)
FTA‑544: 4-channel isolated AO (4–20mA/0–10V), equipped with AO3401
FTA‑542: 8-channel non-isolated AO, economical
FTA‑441: 16-channel common-ground terminal board for DI (equipped with DI3301)
FTA‑442: 16-channel isolated DI terminal board (equipped with DI2301)
Get a Quote