DO2401
Description
Product Description
I. Official Standard Core Parameters
1. Basic Specifications
Model: DO2401 16-channel 24VDC Triple Redundant Digital Output Module
Material Number: 7400209-030
Channel Quantity: 16 channels, point-to-point isolation (optical isolation)
Output Type: Solid-state output (source type / sink type programmable)
Rated Voltage: 24VDC, operating range 15–30VDC
Current per Channel: Rated 2A, maximum 3A (single channel)
Total Module Current: Maximum 8A
Conduction Voltage Drop: ≤ 0.8V (@2A)
Response Time: ≤ 1ms (on→off / off→on)
System Architecture: TMR Triple Redundancy, three independent drives, three-out-of-two voting
Safety Level: IEC61508, TÜV Certification SIL3
Insulation Voltage Rating: Field↔Backplane 1500VAC, complete isolation between channels
Fault Diagnosis: Open circuit / short circuit / overload / overvoltage diagnosis, readback verification, FVD mandatory value diagnosis
Protection Configuration: Channel current limiting, surge suppression, reverse polarity protection, overload self-recovery
Hot Swap: Supports online replacement, no system disturbance
Redundancy Capability: Supports dual DO2401 redundancy, automatic master-slave switching
Power Supply Method: Backplane 24VDC (+/-10%)
Overall Power Consumption: Approximately 6W
Operating Temperature: -40℃ to + 70℃
Storage Temperature: -55℃ to + 85℃
Certifications: CE, UL, CSA, ATEX/IECEx, TÜV SIL3
Installation Method: Tricon Host Frame / Expansion Frame I/O Slot
Matching Terminal Board: 9662-210 16-channel Isolated Output Terminal Board
Dimensions: 170×40×200mm
Product Weight: Approximately 1.4kg
2. Panel Indicator Light Meanings
PWR (Green): Module power supply is normal
OK (Green): TMR voting is normal, module operation is normal
FAULT (Red): Module / Channel / Diagnostic Fault
CH01–CH16 (Yellow): Channel output status / Fault indication
3. Main Product Features
Drive Equipment: Electromagnetic valves, relays, contactors, indicator lights, valve actuators, alarm horns
Load Type: 24VDC Inductive / Resistive Load, compatible with NPN/PNP Load
Data Interaction: TriBus Backplane High-Speed Communication, Triple Redundant Voting Output
Configuration Software: TriStation, configurable fault safety state, output delay, alarm threshold
II. Typical Application Scenarios
ESD Emergency Stop: Emergency Cut-off Valve, Blow-off Valve, Interlock Relay Drive
BMS Combustion Management: Ignition Transformer, Fuel Valve, Blow-off Valve Control
Unit Control: Compressor / Steam Turbine Anti-Surge Valve, Electromagnetic Valve, Interlock Actuator
Process Interlock: Safety Cut-off Valve, Drain Valve, Alarm Indicator Light, On-site Sound and Light Alarm
III. Differentiation of Similar Output Modules on the Same Platform
DO2401: 16-channel 24VDC, point-to-point isolation, each channel 2A, SIL3, General-purpose Safety Output
DO6603: 32-channel 24VDC, common ground type, each channel 0.5A, SIL3, High-density Low-cost
DO2302: 16-channel 120/230VAC, SIL3, High-voltage AC Actuator Specialized