DI6503
Description
Product Description
I. Official Standard Core Parameters
1. Basic Specifications
Model: DI6503 32-channel 24VDC Triple Redundant Digital Input Module
Material Number: 7400208-040
Channel Quantity: 32 channels, point-to-point isolation (optical isolation)
Input Type: Wet contact (active) / Dry contact (passive) compatible, Sink/Source universal
Rated Voltage: 24VDC, operating range 15–30VDC
Conduction Threshold: ≥18VDC (ON); ≤5VDC (OFF)
Input Current: 5–10mA per channel (typical)
Response Time: <10ms (software programmable filtering)
System Architecture: TMR Triple Redundancy, three independent acquisition, three-out-of-two voting
Safety Level: IEC61508, TÜV Certified SIL3
Insulation Voltage: Field ↔ Backplane 1500VAC, complete isolation between channels
Fault Diagnosis: Open circuit / Short circuit / Overpressure / Load fault, readback verification, FVD mandatory value diagnosis
Protection Configuration: Each channel current limiting, surge suppression, reverse polarity protection
Hot Swap: Supports online replacement, no system disturbance
Redundancy Capability: Supports dual DI6503 redundancy, automatic master-slave switching
Power Supply Method: Backplane 24VDC (+/-10%)
Overall Power Consumption: Approximately 8W
Operating Temperature: -40℃ to + 70℃
Storage Temperature: -40℃ to + 85℃
Certifications: CE, UL, CSA, ATEX/IECEx, TÜV SIL3
Installation Method: Tricon Host Frame / Expansion Frame I/O Slot
Matching Terminal Board: 9661-210 32-channel Isolated Terminal Board
Dimensions: 225×112×40mm
Product Weight: Approximately 2.2kg
2. Panel Indicator Light Meanings
PWR (Green): Module power supply is normal
OK (Green): TMR voting is normal, module operation is normal
FAULT (Red): Module / Channel / Diagnostic Fault
CH01–CH32 (Yellow): Channel input status / Fault indication
3. Main Product Features
Acquisition Signals: Emergency stop button, limit switch, valve feedback, proximity switch, flame detector, pressure / level / temperature switch
Load Type: 24VDC Switching Quantity, compatible with NPN/PNP sensors
Data Interaction: TriBus Backplane High-speed Communication, Triple Redundant Voting Input
Configuration Software: TriStation, configurable filtering time, safety default values, alarm thresholds
II. Typical Application Scenarios
ESD Emergency Stop: Emergency stop button, safety barrier, valve feedback acquisition
BMS Combustion Management: Flame detector, ignition switch, fuel valve status monitoring
F&G Fire and Gas System: Smoke / Temperature / Combustible Gas Detector Switch Signal
Unit Control: Compressor / Turbine overspeed, shaft vibration, interlock switch status acquisition
Process Interlock: Critical pressure / level / temperature switch, safety valve feedback monitoring
III. Differentiation of Similar Input Modules on the Same Platform
DI6503: 32-channel 24VDC, point-to-point isolation, SIL3, high density, high anti-interference, priority for critical safety signals
DI2301: 32-channel 24VDC, point-to-point isolation, SIL3, standard type, universal critical signals
DI3301: 32-channel 24VDC, common ground type, SIL3, high density, low cost, ordinary signals
DI2302: 16-channel 120/230VAC, SIL3, dedicated for high-voltage AC switch signals
Get a Quote