DI3301
Description
Product Description
I. Official Standard Core Parameters
1. Basic Specifications
Model: DI3301 32-channel 24VDC Triple Redundant Digital Input Module
Material Number: 7400208-030
Channel Quantity: 32 channels (common ground design, not point-to-point isolation)
Input Type: Wet Contact (Active) / Dry Contact (Passive) Compatible
Rated Voltage: 24VDC, Operating Range 15–30VDC, Maximum 33VDC
Input Current: Typical 1mA, Maximum 5mA
Input Impedance: >30kΩ (without board), ≈3kΩ (with board)
Response Time: <10ms (On→Off / Off→On)
System Architecture: TMR Triple Redundant Architecture, Three Independent Acquisition Circuits, Three-out-of-Two Voting Logic
Safety Level: Compliant with IEC61508, TÜV Certification SIL3 Level
Insulation Level: 1500VAC Isolation between Field Side and Backplane, Common Ground between Channels (No Isolation)
Fault Diagnosis: Open Circuit / Short Circuit / Overpressure / Load Fault Detection, Forced Value Diagnosis FVD, Signal Readback Verification
Protection Configuration: Each Channel Current Limiting Protection, Surge Suppression
Hot Swap Function: Supports Online Non-Maintenance Plug-and-Play Replacement
Redundancy Capacity: Supports Dual DI3301 Redundancy, Master-Slave Automatic Switching
Power Supply Method: Backplane 24VDC Power Supply (±10%)
Overall Power Consumption: Approximately 5W
Operating Temperature: -40℃ to + 70℃
Storage Temperature: -55℃ to + 85℃
Certification: CE, UL, CSA, ATEX/IECEx, TÜV SIL3
Installation Method: Tricon Host Frame / Expansion Frame I/O Slot
Matching Terminal Board: 9661-210 32-Channel Common Ground Terminal Board
Dimensions: 170×40×200mm
Product Weight: Approximately 1.42kg
2. Panel Indicator Light Meanings
PWR (Green): Module Power Supply Normal
OK (Green): Triple Redundant Voting Normal, Module Running Normal
FAULT (Red): Module / Channel / Diagnostic Fault
CH01–CH32 (Yellow): Channel Input Status / Fault Indication
3. Main Product Features
Acquisition Signals: Limit Switches, Emergency Stop Buttons, Proximity Switches, Relay Contacts, Valve Feedback, Field Equipment Status
Load Type: 24VDC Switching Signals, Compatible with NPN/PNP Type Sensors
Data Interaction: TriBus Backplane High-Speed Communication, Triple Redundant Voting Input
Configuration Software: TriStation, Can Set Input Filtering, Safety Default Values, Alarm Thresholds
II. Typical Application Scenarios
ESD Emergency Stop: Emergency Stop Button, Safety Barrier, Emergency Cut-off Valve Feedback Acquisition
BMS Combustion Management: Flame Detector, Ignition Switch, Fuel Valve Status Monitoring
Unit Control: Compressor / Steam Turbine Shaft Vibration Switch, Overspeed Switch, Interlock Status Acquisition
Process Interlock: Pressure / Level / Temperature Switch, Safety Valve Feedback, Field Equipment Status Monitoring
III. Differentiation of Similar Input Modules on the Same Platform
DI3301: 32-channel 24VDC, Common Ground Type, SIL3, High Density Low Cost, Suitable for Large-scale Ordinary Safety Signal Acquisition
DI2301: 32-channel 24VDC, Point-to-Point Isolation, SIL3, Strong Anti-Interference, Suitable for Critical Safety Signal Acquisition
DI2302: 16-channel 120/230VAC, SIL3, Special for High Voltage AC Switch Signals