D06603
Description
I. Core Parameters (DO6603 Official Standard Version)
1) Basic Specifications
Model: DO6603 (8-Ch Digital Output, TMR, 24VDC)
Part Number: 7400136
Number of Channels: 8 channels / module (point-to-point isolation)
Output Type: Isolated Solid State Relay Output (SSR), Dry Contact / Wet Contact Optional
Rated Voltage: 24VDC (±10%)
Single Channel Current: Maximum 2A (Resistive Load)
Output Mode: Normally Open (NO) / Normally Closed (NC) Programmable Software
Architecture: TMR Triple Redundancy (Three Circuit Independent Outputs, 2-of-3 Voting)
Safety Level: SIL3 (IEC 61508, TÜV Certification)
Isolation: Field ↔ Backplane 1500VAC; Channel-to-Channel Complete Isolation
Response Time: <1ms (High Speed)
Diagnosis: Open Circuit / Short Circuit / Overload, Load Fault, Readback Check, Over Temperature, Contact Adhesion
Protection: Each Channel Electronic Fuse, Surge Protection
Hot Swap: Supports Online Replacement (System Continues)
Redundancy Capability: Supports Dual DO6603 Redundancy (Primary/Backup Automatic Switching)
Power Supply: 24VDC (Backplane, ±10%)
Power Consumption: Approximately 8W
Operating Temperature: 0℃ ~ +60℃
Storage Temperature: -40℃ ~ +85℃
Certification: CE, UL, CSA, ATEX/IECEx, TÜV SIL3
Installation: Tricon Host Rack / Expansion Rack I/O Slot
Matching Terminal Board: 9661-210 (8 Point Isolated Terminal Board)
Dimensions (L×W×H): Approximately 170 × 40 × 200 mm
Weight: Approximately 0.8 kg
2) Panel Indicator Lights
PWR (Green): Module Power Supply Normal
OK (Green): TMR Voting Normal, Module Running Normal
FAULT (Red): Module / Channel / Diagnostic Fault
CH01–CH08 (Yellow): Channel Output Activation / Fault Indication
3) Key Features of DO6603
Drive Object: Electromagnetic Valve, Relay Coil, Contactor, Alarm Light, Sound and Light Alarm, ESD Shut-off Valve
Load Type: 24VDC DC Load (Resistive / Inductive, Inductive Requires Continuity Diode)
Data Interaction: TriBus Backplane High-Speed Communication, TMR Voting Output
Configuration Tools: TriStation (Configure Channel Mode, Safety-Reliable Values, Alarm Thresholds)
II. Typical Application Scenarios
ESD Emergency Stop: Drive ESD Shut-off Valve, Emergency Stop Relay
BMS Combustion Management: Drive Ignition Transformer, Fuel Valve, Blow-off Valve
Unit Control: Drive Compressor / Turbine Emergency Stop Electromagnetic Valve
Interlock Alarm: Drive Field Alarm Light, Sound and Light Alarm, Horn
III. DO6603 Comparison (Same Platform DO Modules)
DO6603: 8 Channels, 24VDC, 2A, SSR, TMR, SIL3, High-Speed < 1ms, Point-to-Point Isolation; Safety Interlock / ESD/BMS
DO6601: 16 Channels, 24VDC, 0.5A, Transistor, TMR, SIL3, Economy Type; Ordinary Alarm Light / Small Relay
DO6604: 8 Channels, 120/230VAC, 5A, Relay, TMR, SIL3; AC Load (Large Contactor / Pump)