CM3201
Description
I. Core Parameters (Official Standard Version of CM3201)
1) Basic Specifications
Model: CM3201 (Communication Module, TMR)
Architecture: TMR Triple Redundancy (Three processors operate independently, median voting)
Port Configuration (per module):
3 × Isolated Optical Serial Ports: RS-232/485 (Software selectable)
2 × Ethernet Ports: 10BaseT (RJ45) + AUI (Old-fashioned coaxial)
Protocol Support:
Serial Ports: Modbus RTU Master/Slave, TriStation, TSAA, Tricon Peer-to-Peer Communication
Network Ports: TCP/IP, UDP/IP, Modbus TCP, TriStation Ethernet
Serial Port Rate: Up to 115.2 kbps (Independent configuration per port)
Network Port Rate: 10 Mbps (Half/Full Duplex)
Isolation: Serial Port ↔ Backplane 1500VAC; Isolation between Ports
Redundancy Capability: Supports Dual CM3201 Redundancy (Automatic Master/Slave Switching)
Power Supply: 24VDC (Backplane, ±10%)
Power Consumption: Maximum 10W
Operating Temperature: -40°C ~ +70°C
Certifications: CE, UL, CSA, ATEX/IECEx, TÜV SIL3
Installation: Trident Host Rack CM Slot (Requires CM Board)
Quantity Limitation: Single Trident Controller Can Install Up to 2 CM3201
Size (D × W × H): Approximately 220 × 169 × 44 mm
Weight: Approximately 1 kg
2) Panel Indicators
PWR (Green): Module Power Supply Normal
OK (Green): TMR Voting Normal, Module Running Normal
FAULT (Red): Module / Port / Diagnostic Fault
COM0–COM2 (Yellow): Serial Port Transmit/Receive Indicator
ETH (Yellow): Ethernet Transmit/Receive Indicator
3) Key Features of CM3201
Connected Objects: DCS, PLC, SCADA, Host Computer, Printer, Other Tricon Systems
Data Interaction: Real-time Read/Write AI/AO/DI/DO, System Status, Alarm, Historical Data
Diagnosis: Port Fault, Protocol Error, Data Verification, Redundancy Switching, Over Temperature
Configuration Tools: TriStation Trident (Configure Ports, Protocols, Addresses, Redundancy)
II. Typical Application Scenarios
SIS ↔ DCS Communication: Modbus TCP/RTU Bidirectional Data Exchange (Interlocking Signals, Process Parameters)
SIS ↔ Host Computer / SCADA: TCP/IP Real-time Monitoring and Operation
SIS ↔ Third-party Devices: RS-485 Modbus Connection Analyzer, Frequency Converter, Instrument
SIS Redundant Communication: Dual CM3201 Redundancy to Ensure Communication Link Continuity
III. Comparison of CM3201 (Same Platform Communication Modules)
CM3201: 3 Serial Ports + 2 Network Ports, TMR, SIL3, General Type; Standard External Communication
CM3202: 2 Network Ports (100Mbps), High-speed Ethernet, No Serial Ports; Large Data / High-speed DCS Connection
CM3203: 4 Serial Ports, High-density Serial Ports, 1 Network Port; Multiple Instruments / Third-party Devices Connection
Get a Quote