AI6700
Description
I. Core Parameters (Official Standard Version of AI6700)
1) Basic Specifications
Model: AI6700 (Analog Input, 8 Ch, High Precision, TMR)
Number of Channels: 8 channels / module (differential, point-to-point isolation)
Signal Type (Software Programmable):
Current: 4–20mA, 0–20mA, ±320mA
Voltage: 0–5V, ±5V, ±10V
Resolution: 16 bits
Accuracy: ±0.05% reading + ±0.05% range (high precision level)
Response Time: <1ms (full channel high-speed synchronization)
Input Impedance: Current 250Ω; Voltage ≥10MΩ (differential)
Isolation: Field ↔ System 1500VAC; Channel-to-channel complete isolation
Diagnosis: Open circuit / short circuit / overrange, FVD, overvoltage / overcurrent, fuse blowout
Safety Level: SIL3 (IEC 61508, TÜV Certification)
Redundant Architecture: TMR triple redundancy (three-channel independent sampling, median voting)
Power Supply: 24VDC (backplane power supply)
Power Consumption: Approximately 12W
Operating Temperature: -40℃ ~ +70℃
Certifications: CE, UL, CSA, ATEX/IECEx, TÜV SIL3
Installation: Trident chassis slot (19 inches)
Matching Terminal Board: 9761-210 (8-point isolated terminal board)
Matching Cable: 4000016-010 (flat cable 1 piece)
2) Panel Indicators
PWR (Green): Module power supply is normal
OK (Green): TMR voting is normal, module is running normally
FAULT (Red): Module / Channel / Diagnostic Fault
CH01–CH08 (Yellow/Green): Channel status (normal / fault)
3) AI6700 vs AI2351 vs AI3721 (Key Differences)
AI6700: 8 differential, 16 bits, <1ms, multi-range, high precision, isolation, SIL3; Key high-precision safety circuits (such as precise pressure, flow, weighing)
AI2351: 8 channels, 24 bits, multiple signals (mA/V/TC/RTD), ultra-high precision; dedicated for temperature / thermocouple / thermoresistor
AI3721: 32 differential, 12/14 bits, 10ms, voltage dedicated, high density; large-scale high-speed voltage acquisition
II. Usage Instructions (Wiring + Configuration + Maintenance)
1) Wiring (with 9761-210 terminal board, differential isolation)
4–20mA two-wire transmitter
Transmitter + → CHx+
Transmitter‑ → CHx-
Shield → SHD (single-ended grounding)
±10V differential sensor
Signal + → CHx+
Signal‑ → CHx-
Shield → SHD
2) Configuration (TriStation Trident)
Hardware slot selection: AI6700
Channel Parameters:
Input Type → 4–20mA / ±10V etc.
Range → Corresponding range
Set filtering, alarm threshold, diagnostic enable
Download configuration, module restart takes effect
3) Fault Troubleshooting
FAULT (Red) on: Channel short circuit / open circuit / overrange → Check wiring, terminal board, sensor
OK (Off): Backplane power supply, firmware, TMR synchronization failure
Signal drift: Check shielding grounding, differential twisted pair, interference source, accuracy calibration
Get a Quote