AI2351
May 18, 2026

AI2351

AI2351 (TRICONEX / Schneider Tricon SIS) Model: AI2351 (Part Number: 7400210-010 / 7400210-100) Brand: TRICONEX (Schneider Tricon Safety Instrumentation System) Position: TMR Triple Redundancy 8-Channel Precision Analog Input Module (AI Card), Tricon High-End SIS System, SIL3, for Critical Safety Circuits (Temperature / Pressure / Flow / Level).

Description

I. Core Parameters (AI2351)

1) Basic Specifications

Model: AI2351 (Analog Input Module, 8 Ch, TMR, High Precision)

Number of Channels: 8 channels / module (triplex isolation, point-to-point isolation)

Signal Type (Software Configuration):

Current: 4–20mA

Voltage: 0–10V, ±10V, 0–5V, 1–5V

Millivolt: ±50mV, ±100mV

Thermocouple: J/K/T/E/R/S/B/N

RTD: Pt100, Pt1000 (2/3/4 wires)

Resolution: 24-bit ADC (per channel independently)

Accuracy: ±0.03% FS @ 25℃ (temperature ±10ppm/℃)

Sampling Rate: 35ms / channel (TMR synchronous sampling)

Common Mode Suppression: 140dB @ 50/60Hz

Isolation: Field ↔ System ≥ 1500VAC; Channel-to-channel ≥ 500VDC

Diagnostic Coverage: 99.9% (IEC 61508)

Safety Level: SIL3 (TÜV Certification)

Redundant Architecture: TMR triple redundancy (three-channel independent sampling, voting output)

Power Supply: 24VDC (module backplane power supply)

Power Consumption: Approximately 12W

Operating Temperature: -40℃ ~ +70℃

Certifications: CE, UL, CSA, ATEX/IECEx, TÜV SIL3

Installation: Tricon mainframe slot (19-inch)

Matching Terminal Board: 9771-210, 9853-610 (16 points, 2 terminal boards with 1 AI2351)

Matching Cable: 4000016-015 (flat cable)

2) Panel Indicators

PWR (Green): Module power supply is normal

OK (Green): TMR voting is normal, module is running normally

FAULT (Red): Module failure / channel failure / diagnostic anomaly

CH01–CH08 (Yellow/Green): Channel status (normal / fault)

3) Key Differences between AI2351 and Ordinary AI Modules (e.g. 3805E)

AI2351: 8 channels, 24 bits, TMR triple redundancy, SIL3, high precision, multiple signal types; high-end safety circuit

3805E: 16 channels, 16 bits, single channel, SIL2, standard accuracy, only 4–20mA/0–10V; general economy

II. Usage Instructions (Wiring + Configuration + Maintenance)

1) Wiring (with 9771-210 / 9853-610)

4–20mA two-wire transmitter: + → CHx+; – → CHx–; shield → SHD

RTD three-wire / four-wire: Use terminal board RTD-specific terminals (requires configuration selection of RTD)

Thermocouple: + → TC+; – → TC–; cold junction compensation (CJC) automatic

2) Configuration (TriStation)

Select AI2351 in hardware slot

Channel Parameters: Input Type → 4–20mA / 0–10V / TC / RTD

Set range, filtering, alarm threshold

Download configuration, module restart takes effect

3) Fault Troubleshooting

RED FAULT: TMR voting inconsistency, channel short circuit / open circuit, over-range → Check wiring, terminal board, configuration

GREEN OK: Backplane power supply, module firmware, TMR synchronization failure

Signal drift: Check shield grounding, thermocouple cold junction compensation, RTD wiring resistance


Get a Quote