I. Core Parameters (9771-210)
1) Basic Specifications
Model: 9771-210 (AI ETP, 16 Points, Configurable V/I, Passive)
Signal Type: Software Configurable - 4–20mA Current or 0–5V/0–10V Voltage (TriStation Configuration Switch)
Channel Count: 16 Points / Board (Half-Length Size, Flexible Group Wiring)
Sampling Resistance: Built-in 250Ω Precision Resistor (4–20mA → 1–5VDC, No External Connection Required)
Input Impedance: Current Mode 250Ω; Voltage Mode High Resistance (≥1MΩ)
Isolation: ≥1500VAC Field - System Isolation, Channel-to-Channel Isolation
Accuracy: ±0.05% FS @ 25℃
Diagnosis: Open Circuit / Short Circuit / Overrange (Current < 4mA or > 20mA, Voltage Overrange)
Safety Level: SIL3 (IEC 61508)
Power Supply: Passive Terminal Board (No 24V Required)
Operating Temperature: -40℃ ~ +70℃
Certifications: CE, UL, CSA, ATEX/IECEx
Installation: 35mm DIN Rail
Compatible Modules: 3700, 3700A, 3703E, 3721 (Tricon 16/32 Point AI)
Cables: Special Flat Cables (Same as 9760/9761 Series)
2) Panel Indicator Lights
CH01–CH16 (Green): Channel Normal (Signal within Valid Range)
FAULT (Red): Any Channel Fault (Open Circuit / Short Circuit / Overrange)
3) Key Differences between 9771-210 and 9760-210/9761-210/9765-210
9771-210: 16 Points, Voltage / Current Configurable, Passive; General Type, Suitable for Mixed Signals (Voltage + Current)
9760-210: 32 Points, Pure Two-Wire 4–20mA, Passive; Standard High Density
9761-210: 16 Points, Pure Two-Wire 4–20mA, Passive; Half-Length Compact
9765-210: 32 Points, Three-Wire 4–20mA, With CJC; Three-Wire + Thermocouple Specialized
II. Usage Instructions (Installation / Wiring / Configuration)
1) Configuration Rules
32 Point AI Module (3700A/3720): 2 Pieces of 9771-210 Connected in Parallel (1–16 Channels, 17–32 Channels)
16 Point AI Module (3703E): 1 Piece of 9771-210 Directly Connected
Hot Swap: Supports Online Replacement, Does Not Affect System Operation
2) Wiring (Voltage / Current Common)
4–20mA Two-Wire Transmitter (Default):
Transmitter + → CHx+
Transmitter - → CHx-
Built-in 250Ω, No External Resistor Required
0–5V/0–10V Voltage Signal (Configuration Switch):
Signal + → CHx+
Signal - → CHx-
Cable: 1.0–1.5mm² Shielded Twisted Pair, Single-Ended Grounding of Shield Layer
3) Configuration Steps (TriStation)
Hardware Configuration Selects Corresponding AI Module (3700/3703E/3721)
Channel Parameter Settings: Input Type → Current (4–20mA) or Voltage (0–5V/0–10V)
Download Configuration, Module Reboot to Take Effect
4) Fault Troubleshooting FAULT Red and bright: Open circuit / Short circuit / Over-range of the channel → Check wiring, power supply of the transmitter, and matching of configuration type
CH Light does not illuminate: Check flat cable, module configuration, and terminal tightening
Unstable signal: Check shielding grounding, cable length, and environmental interference