9765-210
May 18, 2026

9765-210

9765-210 Terminal Board (TRICONEX / Schneider Tricon SIS) Model: 9765-210 Brand: TRICONEX (Schneider Tricon Safety Instrumentation System) Location: 32-point three-wire 4–20mA analog current input terminal board (with cold junction compensation, passive), specially designed for three-wire transmitters + thermocouple / thermoresistor mixed scenarios, with the same number of points as 9760-210, stronger wiring and compensation capabilities.

Description

I. Core Parameters (9765-210)

1) Basic Specifications

Model: 9765-210 (AI ETP, 3-Wire 4–20mA, 32 Points, 250Ω, CJC)

Signal Type: Three-wire 4–20mA Current Input (Supports Two-wire Compatibility)

Channel Count: 32 Points / Board (1 Direct Connect 32 Channels)

Sampling Resistance: 250Ω Precision Metal Film (4–20mA → 1–5VDC)

Input Impedance: 250Ω (Fixed)

Cold Junction Compensation (CJC): Built-in High Precision Temperature Sensor, Supports Thermocouple (TC) Cold Junction Compensation

Isolation: ≥1500VAC Field - System Isolation, Channel-to-Channel Isolation

Accuracy: ±0.05% FS @ 25℃; CJC Accuracy ±0.5℃

Resolution: 16bit (Dependent on AI Module)

Diagnosis: Open Circuit / Short Circuit / Overrange (<4mA or >20mA), CJC Fault

Safety Level: SIL3 (IEC 61508)

Power Supply: Passive Terminal Board (No 24V Required)

Operating Temperature: -40℃ ~ +70℃

Certification: CE, UL, CSA, ATEX/IECEx

Installation: 35mm DIN Rail

Compatible Modules: 3700A, 3704E, 3720 (Tricon 32 Point AI)

Cables: Special Flat Cables (Same as 9760 Series)

2) Panel Indicator Lights

CH01–CH32 (Green): Channel Normal (4–20mA)

FAULT (Red): Any Channel Fault (Open Circuit / Short Circuit / Overrange / CJC Exception)

3) Key Differences between 9765-210 and 9760-210/9761-210

9765-210: 32 Points, Three-wire, With CJC; Suitable for Three-wire Transmitter + Thermocouple Mixed Circuit

9760-210: 32 Points, Two-wire, Without CJC; Most Common, Pure 4–20mA Two-wire

9761-210: 16 Points, Two-wire, Without CJC; Semi-long, Grouped Wiring

4) Family Positioning

9765-210: 32 Points, Three-wire + CJC (Preferred for Mixed Signal)

9760-210: 32 Points, Two-wire 4–20mA (Standard)

9761-210: 16 Points, Two-wire 4–20mA (Grouped)

9760-410: 32 Points, Voltage Input (0–5V/0–10V)

II. Usage Instructions (Installation / Wiring / Maintenance)

1) Configuration Rules

32 Point AI Module (3700A/3704E): 1 Unit 9765-210 Direct Connect (1–32 Channels)

Hot Swap: Supports Online Replacement, Does Not Affect System Operation

2) Wiring (Three-wire 4–20mA Transmitter + CJC)

Three-wire Transmitter:

Transmitter + → CHx+

Transmitter - → CHx-

Transmitter Ground → CHx GND (Special for Three-wire)

Two-wire Compatibility: Short Circuit GND to CHx-

Thermocouple (TC) Cold Junction Compensation: TC+ → CHx+

TC‑ → CHx‑

Built-in CJC automatic compensation terminal board temperature

Cable: 1.0–1.5mm² shielded twisted pair, single-ended grounding of the shielding layer

Resistor: Built-in 250Ω, no additional external component required

3) Fault troubleshooting

FAULT red light on: Open circuit / short circuit / <4mA/ > 20mA / CJC fault → Check wiring, transmitter power supply, CJC sensor

CH light not on: Check flat cable, module configuration, 24V power supply

Unstable signal: Check shielding grounding, cable length, terminal tightening


Get a Quote