7400213-100
May 18, 2026

7400213-100

7400213-100 (TRICONEX / Schneider Tricon FTA Terminal Base / I/O Interface Backplate) Model: 7400213-100 Brand: TRICONEX (Schneider Tricon SIS) Type: Tricon I/O Module FTA (Field Terminal Assembly) - Field Wiring Base for I/O Modules Position: "Wiring Hub" between I/O Module and Field Cables, TMR Tri-Redundancy Component Compatibility: Tricon 3700/4000 Series AI/AO/DI/DO Modules (such as 4000164-520, 3720), not communication card base. 1. Product Overview (Core Parameters) 1) Basic Information Model: 7400213-100 (FTA Terminal Base) Function: External Wiring of I/O Module + Signal Isolation + Lightning / Surge Protection + Triple Redundancy Signal Conversion Architecture: TMR Tri-Redundancy (Consistent with Tricon Controller / I/O) Ports: 24 Wiring Terminals (Screw Type,便于 Field Wiring) Compatible Modules: 3700/4000 Series Standard I/O Cards (DI/DO/AI/AO) Signal Isolation: 500VAC Isolation, Anti-interference, Lightning Protection Power Supply: Powered by I/O Module Backplate, No Additional Power Required Temperature: -40℃ ~ +70℃ (Industrial Wide Temperature) Certifications: CE, UL, CSA, SIL3, ATEX 2) Function (In One Sentence) 7400213-100 = "Field Wiring Panel" of Tricon I/O Module: Converts internal signals of 3700/4000 I/O Modules into screw terminals that can be directly connected to field cables Provides overvoltage / overcurrent / ESD Protection, protecting I/O Module Supports Hot Swap: Base Wiring remains unchanged, can directly replace the upper I/O Module 3) Differences from Other Baseplates (At a Glance) 7400206-100 (CM2201): Internal I/O Slot Baseplate (for Module Insertion) 7400213-100: FTA External Wiring Baseplate (below the module, for connecting field cables) 7400280-100: TCM Communication Card (4351A) Special FTA Baseplate

Description

7400213-100 (TRICONEX / Schneider Tricon FTA Terminal Base / I/O Interface Backplate)

Model: 7400213-100

Brand: TRICONEX (Schneider Tricon SIS)

Type: Tricon I/O Module FTA (Field Terminal Assembly) - Field Wiring Base for I/O Modules

Position: "Wiring Hub" between I/O Module and Field Cables, TMR Tri-Redundancy Component

Compatibility: Tricon 3700/4000 Series AI/AO/DI/DO Modules (such as 4000164-520, 3720), not communication card base.

1. Product Overview (Core Parameters)

1) Basic Information

Model: 7400213-100 (FTA Terminal Base)

Function: External Wiring of I/O Module + Signal Isolation + Lightning / Surge Protection + Triple Redundancy Signal Conversion

Architecture: TMR Tri-Redundancy (Consistent with Tricon Controller / I/O)

Ports: 24 Wiring Terminals (Screw Type,便于 Field Wiring)

Compatible Modules: 3700/4000 Series Standard I/O Cards (DI/DO/AI/AO)

Signal Isolation: 500VAC Isolation, Anti-interference, Lightning Protection

Power Supply: Powered by I/O Module Backplate, No Additional Power Required

Temperature: -40℃ ~ +70℃ (Industrial Wide Temperature)

Certifications: CE, UL, CSA, SIL3, ATEX

2) Function (In One Sentence)

7400213-100 = "Field Wiring Panel" of Tricon I/O Module:

Converts internal signals of 3700/4000 I/O Modules into screw terminals that can be directly connected to field cables

Provides overvoltage / overcurrent / ESD Protection, protecting I/O Module

Supports Hot Swap: Base Wiring remains unchanged, can directly replace the upper I/O Module

3) Differences from Other Baseplates (At a Glance)

7400206-100 (CM2201): Internal I/O Slot Baseplate (for Module Insertion)

7400213-100: FTA External Wiring Baseplate (below the module, for connecting field cables)

7400280-100: TCM Communication Card (4351A) Special FTA Baseplate

II. Instructions for Use (Installation / Wiring / Maintenance)

1) Installation and Mounting

Installation location: Directly install below the I/O module (at the rear or side FTA rail of the chassis)

Fixation method: Rail clips + 2 fixing screws (anti-vibration)

Module pairing:

Upper side insert 3700/4000 I/O module (such as 4000164-520 DI)

Lower side connect 7400213-100 FTA base

Hot swapping: Supports online replacement of I/O modules, FTA wiring does not need to be moved

2) Wiring Points (Most commonly used in the field)

Terminal arrangement: 24 screw terminals, grouped by module signal type (DI/DO/AI/AO)

Wiring norms:

Signal lines: Single-core / multi-core shielded wires, shielded layer grounded at one end

Power lines: 24VDC positive and negative corresponding terminals,严禁reverse connection

Redundant signals: Three redundant channels are respectively connected to corresponding terminals, cannot be mixed

Grounding: Reliable connection between FTA base shell and chassis ground (critical for anti-interference and lightning protection)

Identification: Each terminal is labeled with signal labels (such as DI1, 24V+, GND)

3) TriStation Configuration

No configuration required: FTA is a pure hardware wiring base, TriStation only recognizes the upper I/O module

Automatic diagnosis: Module faults, wiring short circuit / open circuit, TriStation will alarm and locate the specific channel

4) Indicator Lights and Diagnosis

No independent indicator lights: Status can be seen on the upper I/O module panel (PASS/FAULT/ACTIVE)

Common faults:

Red light of FAULT on: Mostly due to on-site wiring short circuit / open circuit, 24V power abnormality, terminal loosening

No signal on channel: Check terminal wiring, shielding grounding, and on-site equipment status

5) Daily Maintenance

Regular inspection: Check the tightness of terminal screws, whether the wiring is aged, and whether the shielding grounding is reliable

Cleaning: Use a dry brush to clean terminal dust after power off

Replacement: FTA damage can be replaced online, no need to stop the machine, no need to rewire


Get a Quote