3504E
Description
Core Configuration
Number of channels: 32 digital input channels
Input type: 24VDC dry contact input
Work architecture: Three-out-of-Two TMR redundant voting mode
Wiring method: Wired at the site using the dedicated FTA terminal board
Supports hot-swappable design, allowing for on-site replacement without downtime Electrical parameters
Module working power supply: 24VDC
Input method: Passive contact closure conducts, no external power supply required
Conduction condition: Signal can be collected when the on-site switch is closed
Grouping form: 8 channels are designed as one group
Electrical isolation: Equipped with reliable isolation protection, resistant to on-site interference
Operating temperature: -40℃ to +70℃
It comes with channel status indicator lights and supports self-check for line faults
Complies with IEC61508 international safety standards Product features
Pure dry contact collection, compatible with various passive switch contacts, with extremely strong versatility
Triple redundant safety design, with strong fault tolerance, and stable operation in high-risk working conditions
32-channel high-density design, significantly saving cabinet installation space
No need to provide signal power supply on-site, wiring is simple, and construction is convenient
Easy configuration operation, compatible with Tricon full series programming software
Industrial wide-temperature design, suitable for complex on-site environments such as chemical and power industries Applicable scenarios
Emergency stop buttons for chemical and petrochemical plants, collection of on-site passive switch signals
Connection of various passive limit switches and travel switches for boilers and steam turbines in power plants
Passive feedback signals from flame probes and gas detectors in F&G fire protection systems
Collection of various mechanical contacts and safety interlock switches without voltage output at the site
Identification of the same series models
3501E: 32 channels, 115V AC/DC input
3502E: 32 channels, 48V AC/DC input
3503EN: 32 channels, 24V wet contacts with active input
3504E: 32 channels, 24V dry contacts without active input
Get a Quote