3502E
Description
Core Configuration
Number of channels: 32 independent isolated digital inputs
Rated input signal: 48V AC/DC
Input format: Supports open and closed normally free configuration
Architecture mode: Three-out-of-two TMR redundant voting
Connection method: Back-end adapter to dedicated FTA field terminal board
Support hot-swapping, online replacement and maintenance without downtime Electrical parameters
Power supply for work: Module power supply 24VDC
Input voltage range: 36V to 60V
Input trigger current: Standard industrial threshold
Channel insulation: Each channel is fully electrically isolated, with strong anti-interference capability
Operating temperature: -40℃ to +70℃
Equipped with self-check function for channel faults and line break diagnosis
Complies with IEC61508 safety standard, with multiple industrial certifications Product features
Triple redundancy safety architecture, without single point failure, meeting the safety requirements for high-risk environments
32 channels of high-density integration, saving cabinet slots and reducing the overall project cost
48V standard industrial signals, compatible with a large number of on-site limit switches and on-site contact signals
Independent photoelectric isolation design, effectively eliminating interference from the site and ground potential difference
The panel is equipped with status indicator lights, making the operation status of the channels clearly visible
Program configuration is simple, compatible with mainstream Tricon programming software Applicable scenarios
48V equipment status signal acquisition in the chemical, petrochemical and oil and gas industries
Connection of discrete safety signals for power plant boilers, turbine auxiliary equipment
Digital signal acquisition for ESD emergency stop system and F&G fire and gas monitoring system
Acquisition of passive contact signals and valve position feedback signals at various high and medium voltage levels in the field
Get a Quote