0923-141-6957
Description
Core parameters
Architecture: TMR triple redundancy (three-out-of-two voting)
Safety level: SIL3 (IEC 61508)
Communication interface: RJ45 Ethernet + internal system bus
Protocol support: Modbus TCP, Tricon proprietary protocol, OPC (optional)
I/O terminals: 8-channel configurable I/O terminals (auxiliary signals)
Operating voltage: 24VDC ±10% (18–30VDC)
Power consumption: Approximately 0.3A / 7W
Operating temperature: -40°C ~ +70°C
Isolation: Electrical isolation between network and system bus
Certifications: SIL3, CE, UL, FM, ATEX Zone 2 / Class I Div 2
Installation: Tricon host slot (standard 19" rack)
Size/Weight: 200×120×40mm / Approximately 0.6kg
Features and benefits
TMR triple redundancy communication: Three independent channels for reception and voting, no single point failure, SIL3 safety communication
Multi-protocol Ethernet: Supports Modbus TCP, etc., seamless connection to DCS, HMI, and upper computer
System expansion and data bridging: Connect remote I/O stations, third-party safety systems, to achieve cross-system data sharing
Comprehensive diagnosis + hot swapping: Real-time diagnosis of communication links, ports, and protocol failures, online replacement without stopping
High anti-interference and safety isolation: Electrical isolation between network side and system side, suitable for industrial strong interference environments
Typical applications
ESD system and DCS communication: Two-way interaction of SIS interlock signals and process parameters
F&G fire protection system networking: Alarm and status upload of fire protection system to DCS / monitoring platform
Remote I/O expansion: Connect remote I/O cabinets to extend the distance for signal acquisition in the field
SIL3-level safe data exchange: Safety communication links in high-risk industrial environments such as chemical, oil and gas, and power industries
Reference of the same series
0923‑141‑6957: TMR Ethernet communication module (this model)
4351A/B: Tricon main processor module
0903‑164‑7921: 16-channel mixed I/O (8DI + 8DO)
0905‑148‑6921: 16-channel analog input (AI)