8300
Description
Core Configuration
Tricon system-specific redundant power module (providing power to the back panel of the chassis)
Input voltage: 120V AC/DC (50/60Hz)
Output voltage: +5V, +12V, +24V (multiple voltage regulators)
Output power: 50W; Maximum total current: 10A
Redundancy method: Supports 1+1 redundancy, dual power supplies in hot standby mode
Installation slots: Standard chassis slots, can be mixed with I/O/communication modules
Status indication: Front panel LED (power normal / fault / overload) Electrical parameters
Input range: 120VAC ±10% / 120VDC ±10%
Output accuracy: ±1% (at full load)
Ripple noise: <50mV (peak-to-peak)
Efficiency: >85% (typical)
Insulation strength: Input / Output isolated from the backplane by 1500VDC
Protection mechanisms: Overvoltage, overcurrent, short circuit, overheating (automatic recovery)
Operating temperature: 0℃ ~ +60℃
Humidity: 5%–95% RH (no condensation)
Power consumption: Self ≤ 8W
Weight: Approximately 1.3kg Product features
SIL3 Safety Level: Meets IEC 61508 standard, with redundant design free of single-point failures
Highly stable power supply: Multiple precision voltage stabilizers, low ripple, ensuring stable operation of CPU/I/O
Redundant hot standby: Dual power supplies operate simultaneously, automatic fault switching occurs, no power outage
Hot-swappable support: Online replacement, without interrupting system operation
Full self-diagnosis: Real-time monitoring and reporting of power supply, output, temperature, and faults to the system
Wide temperature resistance and anti-interference: Industrial-grade EMI/EMC protection, suitable for harsh industrial conditions in chemical and power industries
High compatibility: Compatible with Tricon full series chassis, plug-and-play Applicable scenarios
Chemical / Petrochemical / Oil and Gas: Core power supply for ESD, BMS, and F&G systems
Power / Energy: Boiler protection, turbine interlock, unit safety control power supply
Redundant Safety System: SIS projects requiring high reliability and long-term operation
Critical Control Loop: Safety instrumented system that cannot be powered off or shut down
Series Differentiation
8300: 120V AC/DC input, 50W, basic model
8301: 230VAC input, 175W, high-power model
8302: 24VDC input, redundant backup model
8300A: Enhanced version, wide temperature range, higher efficiency
Get a Quote