3301
April 24, 2026

3301

DI3301 | Triconex Trident Series Basic Information Model: DI3301 Device: SIS Safety System Digital Input Module Architecture: TMR Triple Modular Redundancy, 2oo3 Voting Protection Level: SIL 3 Detailed Parameters Channels 32 Isolated Digital Inputs Signal Specifications Rated: 24 VDC On Threshold: ≥18 VDC Off Threshold: ≤5 VDC Input Current: ≈ 5 mA / Point Isolation & Diagnosis Field / System Electrical Isolation Dielectric Withstand Voltage: 1500 VAC Loop Fault Self-Diagnosis: Wire Break and Short Circuit Detection Hot Swappable Support Environment Operating Temperature: −40°C ~ +70°C Functions & Applications Field Discrete Signal Collection: Pressure Switches, Liquid Level Switches, Valve Feedback, Equipment Start-Stop Status, Local Buttons, Relay Dry Contacts Applicable to: ESD, BMS, F&G Safety Interlock Systems

Description

3301(4 (1).jpg

3301(3 (1).jpg

3301(2 (1).jpg

3301 (1).jpg

DI3301 | Triconex Trident Series

Basic Information

Model: DI3301

Device: SIS Safety System Digital Input Module

Architecture: TMR Triple Modular Redundancy, 2oo3 Voting

Protection Level: SIL 3

Detailed Parameters

Channels

32 Isolated Digital Inputs

Signal Specifications

Rated: 24 VDC

On Threshold: ≥18 VDC

Off Threshold: ≤5 VDC

Input Current: ≈ 5 mA / Point

Isolation & Diagnosis

Field / System Electrical Isolation

Dielectric Withstand Voltage: 1500 VAC

Loop Fault Self-Diagnosis: Wire Break and Short Circuit Detection

Hot Swappable Support

Environment

Operating Temperature:

−40°C ~ +70°C

Functions & Applications

Field Discrete Signal Collection:

Pressure Switches, Liquid Level Switches, Valve Feedback, Equipment Start-Stop Status, Local Buttons, Relay Dry Contacts

Applicable to: ESD, BMS, F&G Safety Interlock Systems


Get a Quote