AI3351 / 3351 Brand: Triconex Schneider Affiliated System: Trident Safety System (SIS/ESD) Module Type: Analog Input Module AI Safety Level: SIL3, TMR Triple Modular Redundancy ## 1. Core Parameters ### Channel Specifications Number of Channels: 32 analog inputs Signal Type: Standard 4~20mA current signal Optional Range: 0~20mA ### Accuracy & Performance Resolution: 15bit Measurement Accuracy: ≤ ±0.05% Full Scale Input Impedance: Approximately 250 Ω Full Channel Cycle Refresh: 50ms ### Isolation & Diagnosis Electrical isolation between field side and system side Comprehensive self-diagnosis: open circuit, short circuit, over-range and sensor fault alarm TMR 2oo3 (Two-out-of-Three) redundant voting, non-stop operation with single-point fault ### Environmental & Electrical Parameters Operating Voltage: 24VDC Operating Temperature: -40℃ ~ +70℃ Support hot swapping and on-site replacement Insulation Withstand Voltage: 1500V AC ## 2. Application Collect 4-20mA analog signals from field transmitters such as pressure, temperature, flow, liquid level and valve position. Applied to SIS/ESD/F&G safety interlock monitoring in chemical, power and oil & gas facilities.

Description

3351(3 (1).jpg

3351(2 (1).jpg

3351 (1).jpg

AI3351 / 3351

Brand: Triconex Schneider

Affiliated System: Trident Safety System (SIS/ESD)

Module Type: Analog Input Module AI

Safety Level: SIL3, TMR Triple Modular Redundancy


## 1. Core Parameters

### Channel Specifications

Number of Channels: 32 analog inputs

Signal Type: Standard 4~20mA current signal

Optional Range: 0~20mA


### Accuracy & Performance

Resolution: 15bit

Measurement Accuracy: ≤ ±0.05% Full Scale

Input Impedance: Approximately 250 Ω

Full Channel Cycle Refresh: 50ms


### Isolation & Diagnosis

Electrical isolation between field side and system side

Comprehensive self-diagnosis: open circuit, short circuit, over-range and sensor fault alarm

TMR 2oo3 (Two-out-of-Three) redundant voting, non-stop operation with single-point fault


### Environmental & Electrical Parameters

Operating Voltage: 24VDC

Operating Temperature: -40℃ ~ +70℃

Support hot swapping and on-site replacement

Insulation Withstand Voltage: 1500V AC


## 2. Application

Collect 4-20mA analog signals from field transmitters such as pressure, temperature, flow, liquid level and valve position.

Applied to SIS/ESD/F&G safety interlock monitoring in chemical, power and oil & gas facilities.