Honeywell 51204168100 (51204168-100) Product Details
Description

Honeywell 51204168100 (51204168-100) Product Details
Model: 51204168100
Brand: Honeywell
Product Type: TDC3000 / TPS / UCN System Digital Output Module (Digital Output Module)
Compatible Systems: TDC3000, TPS, Experion PKS UCN Control System
I. Product Overview
51204168100 is a digital output module of Honeywell UCN network, belonging to the I/O component of TDC3000/TPS control system. It is used to convert system control signals into switch quantity signals that can be received by on-site equipment, achieving control of devices such as solenoid valves, indicator lights, relays, and motor start-stop circuits.
II. Core Specification Parameters
Number of channels: 16 independent digital outputs
Output type: Transistor / Dry Contact Output (compatible with 24V DC/120V AC load)
Output capacity:
Maximum load per channel: 2A @ 30V DC / 1A @ 120V AC
Total load: ≤ 16A (entire module)
Isolation characteristics: Full electrical isolation between channels, system side - field side (with withstand voltage ≥ 1500V AC)
Response time: ≤ 10ms
Operating voltage: 24V DC system power supply
Operating environment:
Temperature: -20℃ ~ +70℃
Humidity: 5% ~ 95% RH (no condensation)
Installation method: Standard DCS cabinet rail installation
Weight: Approximately 1.2kg
Guarantee: Original factory 12-month standard guarantee
III. Main Functions
16 independent outputs: Each channel can be independently controlled without interference.
High isolation protection: Effectively blocks on-site strong electric interference, protecting the safety of the system controller.
Overcurrent protection: Each channel has built-in overcurrent protection to prevent short circuits from damaging the module.
Status indication: Panel LED displays the output status of each channel (ON/OFF) in real time.
Hot-swappable support: Supports online insertion and removal, without affecting the normal operation of the system.
Wide load compatibility: Compatible with various types of on-site loads such as DC and AC, with flexible application.
IV. System Adaptation and Pairing Components
Adaptation controller: HPM (High Performance Process Manager), APM (Advanced Process Manager)
Pairing FTA terminal board: Needs to be used in combination with the corresponding 16-channel DO FTA (such as 51204166 series)
Compatible systems: TDC3000, TPS, Experion PKS UCN
V. Installation and Usage Tips
The module is installed on the standard cabinet rail to ensure firm fixation and good ventilation.
Output cables use shielded cables, and are laid separately from power cables to reduce interference.
Capacitive loads (solenoid valves, coils) need to be connected in parallel with shunt diodes (DC) / RC absorbers (AC) to suppress reverse electromotive force.
The single-channel load current should not exceed the rated value to avoid overheating damage.
Before wiring, confirm the power polarity, load type, and voltage level to prevent incorrect connection.
VI. Order Information
Order number: 51204168100
Product name: 16-channel digital output module (UCN system)
Matching components: Need to purchase the corresponding FTA terminal board (such as 51204166-125/175) separately
Get a Quote