6200043
Description


2. Main Features
Model: 6200043
Type: Inductive proximity sensor
Detection target: All metal materials
Supply voltage: 10–30 V DC
Output structure: 3-wire DC
Max load current: ≤ 200 mA
Protection class: IP67 dustproof and waterproof
Working temperature: -25 °C ~ +70 °C
Built-in reverse polarity, overvoltage and short-circuit protection
Vibration resistant, high stability for continuous operation
3. Safety Precautions
Cut off power before installation and wiring.
Do not apply voltage beyond 10–30 V DC.
Avoid reverse power connection to prevent sensor damage.
Install away from high-power motors and strong magnetic interference sources.
Do not disassemble or modify the sensor arbitrarily.
Prevent heavy impact, oil pollution and long-term wet environment.
4. Installation Guide
Fix the sensor with locking nut or mounting bracket.
Maintain rated sensing distance from metal target.
Mount perpendicular to the detected surface for best sensitivity.
Do not place extra metal parts near the sensing front.
Route the cable properly, avoid sharp bending and hard pulling.
5. Wiring Definition
Brown:DC +10~30 V Power
Blue:DC 0 V Ground
Black:Signal output
Shield:Ground connection only at controller side
6. Operation Instruction
Wire strictly according to the standard definition.
Power on, the sensor enters standby mode.
When metal enters effective detection range, indicator lights up and output activates.
When metal leaves, output resets and indicator turns off.
Suitable for direct connection to PLC, relay and automation controller input.
7. Troubleshooting
No indicator light: Check power supply and wiring integrity.
Always output ON: Metal target too close or surrounding metal interference.
Signal unstable flickering: Loose wiring, vibration or power fluctuation.
Light on but no output: Signal wire broken or load faulty.
8. Maintenance
Clean dust and iron scraps on the sensing surface regularly.
Check mounting tightness and cable wear periodically.
Avoid long-term high temperature and corrosive gas environment.
Replace immediately if shell crack or cable aging occurs.