Honeywell 9967295 Product Description (620 System I/O Module) Model: 9967295 (General Model: 621-9967) Brand: Honeywell Series: 620 System / 621 Series I/O Card Type: 16-channel Digital Output Module
Description

c
Model: 9967295 (General Model: 621-9967)
Brand: Honeywell
Series: 620 System / 621 Series I/O Card
Type: 16-channel Digital Output Module (DO) Relay Output Type
I. Basic Overview
9967295 is a standard 16-channel relay digital output card in the 620/621 series DCS of Honeywell, used to control external electromagnets, indicator lights, contactors, alarm devices, etc., providing dry contact / relay isolation output. It is widely used in power plants, chemical plants, petrochemical plants, etc., for industrial process interlock and control circuits.
II. Core Specification Parameters
Channel Number: 16 independent relays outputs
Contact Type: SPDT (Single-Pole Double-Throw) Relay
Contact Capacity:
240 VAC / 30 VDC: 5A (resistive load)
Maximum Switching Power: 1250 VA / 150 W
Isolation: Channel - Backplane Full Electrical Isolation (2500 Vrms)
Power Supply: 24 V DC Backplane Power Supply
Power Consumption: < 8 W
Installation: Standard 19-inch Rack, Supports Hot Swap
Status Indicators: Independent LED (ON), PWR, FAULT Indicator Lights per Channel
Operating Temperature: -40°C ~ +70°C
Humidity: 5% ~ 95% RH (No Condensation)
MTBF: > 1,000,000 Hours
Certifications: UL, CE, CSA, Class I Div 2 Explosion-proof (Optional)
III. Functional Features
16-channel Independent Relays Output
Each Channel Independent SPDT Relay, No Shared Common Terminal
Supports Normally Open (NO) / Normally Closed (NC) Flexible Wiring
Channel-to-Channel Complete Isolation to Prevent Crosstalk and Short Circuit Spread
Industrial-grade Reliability
Silver Alloy Contacts, Low Contact Resistance, Long Life
Mechanical Life: > 1×10⁷ Times; Electrical Life: > 2×10⁷ Times
Strong Anti-interference (Compliant with EN 61000-6-2/4 EMC Standards)
Full Metal Shielding, Suitable for Harsh Industrial Environments
Installation and Maintenance
Each Channel LED Real-time Displays Output Status
Plug-in While Powered, Online Replacement Does Not Affect System
Can Be Mixed with 621-9937 (DI), 621-9939 (AI), 623-5020 (CPU) on the Same Rack
IV. Typical Applications
Equipment Start/Stop Control (Pumps, Fans, Valves)
Alarm and Fault Indication Circuits
Safety Interlock System (ESD)
Electromagnetic Valve Drive
Indicator Lights, Alarmers, Relay Coil Control
V. Model Comparison
9967295: General Material Number
621-9967: Standard Model (621 Series DO Card)
621-9967R: Redundant Type
621-9968: 8-channel Relay Output (Simplified Version)