FBC01
Description
FBC01 (P0916PWOC)
Basic Information
Model: FBC01 (Part Number: P0916PWOC)
Manufacturer: Foxboro (Schneider Electric)
Type: 32-Channel Non-Isolated Analog Input Module
System: I/A Series DCS
Status: Obsolete (DCS spare part)
Core Specifications
Input Channels: 32 channels (non-isolated)
Signal Range: 0–20 mA DC (compatible with 4–20 mA transmitters)
Resolution: 12-bit
Accuracy: ±0.1% of span (typical)
Conversion Time: 6 ms per channel
Settling Time: 0.55 seconds (to ±0.1% of final value)
Filter: 5 Hz low-pass filter (3 dB point)
Power Supply: 24 VDC ±10%
Power Consumption: Approx. 6 W
Operating Temperature: -40 °C to +70 °C
Environmental Rating: ISA S71.04 Class G3 (harsh industrial environments)
Mounting: Standard I/A Series baseplate
Dimensions: 19" rack-mountable, 1U height
Key Features
High-Density Input: 32 channels in a single module, reducing cabinet space and wiring costs.
Fieldbus Compatibility: Connects to I/A Series redundant fieldbuses for reliable data transmission.
Noise Filtering: Built-in 5 Hz low-pass filter suppresses high-frequency electrical noise from industrial environments.
Hot-Swappable: Can be replaced without shutting down the system (with redundant fieldbuses).
Diagnostics: On-board status LEDs and DCS-based diagnostic tools for fault detection.
Typical Applications
Process Industries: Chemical, petrochemical, oil & gas (monitoring 4–20 mA transmitters for flow, pressure, level, temperature).
Power Generation: Data acquisition from boiler sensors, turbine transmitters, and auxiliary equipment.
Water Treatment: Monitoring of flow meters, pressure sensors, and level transmitters.
Legacy System Upgrades: Replaces older Foxboro I/O modules in existing DCS installations.
Installation & Wiring
Mounting: Install on I/A Series baseplate in a control cabinet.
Power: Connect 24 VDC power (observe polarity).
Field Wiring: Connect 0–20 mA signals from transmitters to module terminals (non-isolated, common ground).
Fieldbus Connection: Attach redundant fieldbus cables to the module’s communication ports.

Get a Quote