140DDI35310
Description
140DDI35310
Modicon Quantum DC Discrete Input Module
32 Points 24VDC Source Input, 4×8 Isolated Groups, Standard Non-Coated
1. General Description
Manufacturer: Schneider Electric
Series: Modicon Quantum 140 Series
Module Type: 24VDC Sourcing Discrete Input Module
Total Channels: 32 points
Group Configuration: 4 groups × 8 channels, group isolation
Slot Occupation: 1 slot, hot swappable
Surface Treatment: Standard non-coated
Weight: Approx 0.45kg
Application: 24VDC PNP sensors, field buttons, limit switches, general industrial digital signal acquisition
2. Electrical Specifications
Rated Input Voltage: 24 VDC
Operating Voltage Range: 19.2 ~ 30 VDC
Input Mode: Sourcing / PNP type
Logic Level Definition
Logic 1 (ON): 11 ~ 30 VDC
Logic 0 (OFF): 0 ~ 5 VDC
Typical Single Channel Input Current: 6mA
Built-in hardware input filter
Response Time: ≤ 1ms
Dielectric Withstand Voltage: 1500Vrms 1 minute (group to backplane)
Maximum Permissible Input Voltage: 35 VDC
Backplane Current Draw: 260mA
Max Power Dissipation: 6W
3. LED Status Indicators
IN0~IN31 Green LED: Individual channel input status indication
ACTIVE Green LED: Module normal bus communication indication
Without fault diagnostic indicator
4. Environmental Conditions
Operating Temperature: 0℃ ~ +60℃
Storage Temperature: -40℃ ~ +85℃
Relative Humidity: 5% ~ 95%, non-condensing
Working Altitude: ≤2000m, derating operation above 2000m
ESD Immunity: Contact 4kV, Air discharge 8kV
Ingress Protection: IP20
5. Mechanical Parameter & Wiring
Overall Dimension: 35 × 122 × 52 mm
Connection Type: Screw terminal block
Applicable Wire Gauge: 0.5 ~ 2.5 mm²
Each group equipped with independent common terminal
6. Wiring Instruction
External field side supplies 24VDC power
Sourcing input: Signal positive connects to input terminal, group common connects to negative pole
Different groups can adopt independent power supply to realize electrical isolation
7. Software Compatibility & Address
Supported Programming Software: Unity Pro, Concept, ProWORX 32
Default Input Address Range: %I0 ~ %I31 (2 words)
Simple configuration, no extra diagnostic setup required