140DAO85300
May 16, 2026

140DAO85300

140DAO85300 Modicon Quantum AC Discrete Output Module

Description

140DAO85300

Modicon Quantum AC Discrete Output Module

32 Outputs, 20–253 V AC, 47–63 Hz, Triac, Standard Non‑Coating, Non‑Fused, No Diagnostic

English Specification Manual (Full Text)


1. General Description

140DAO85300 is a 1‑slot standard high‑voltage AC discrete output module (triac, 4×8 grouped, non‑fused, no diagnostics) for Schneider Electric Modicon Quantum PLC. It provides 32 AC solid‑state (triac) output channels, arranged as:
  • Outputs: 4 groups × 8 channels (4×8 grouping, group‑to‑group isolation)

Designed for high‑voltage AC applications (115/230 V AC) requiring dense I/O, group isolation, and basic ON/OFF control (no on‑board fusing or fault diagnostics).
  • Manufacturer: Schneider Electric

  • Series: Modicon Quantum (140 Series)

  • Module Type: AC Discrete Output Module, Triac, 32‑Ch (4×8), Standard Non‑Coating, Non‑Fused, No Diagnostic

  • Total Outputs: 32 points (4 groups × 8 ch)

  • Output Grouping: 4 groups × 8 ch (group isolated, common per group)

  • Form Factor: 1 slot, hot‑swappable

  • Coating: Standard non‑conformal coating

  • Weight: ~0.45 kg

  • Key Feature: 32×Triac Out, 20–253V AC, 47–63Hz, 4×8 Group Isolation, Standard Non‑Coating, Non‑Fused, No Diagnostic

  • Application: 115/230V AC contactors, solenoids, lamps, small motors; general‑purpose machinery requiring high‑voltage AC control


2. Electrical Specifications

Outputs (32 × Triac, 20–253 V AC, 4×8 Groups)

  • Output Type: Solid‑state (triac), zero‑crossing

  • Operating Voltage: 20–253 V AC

  • Nominal Voltage: 115 / 230 V AC

  • Frequency: 47–63 Hz

  • Load Current (per channel):

    • 20–253 V AC: 1 A RMS max

  • Total Module Current: 16 A RMS max (continuous)

  • Group Current: 4 A RMS max per group

  • Surge Current (per channel): ≤ 2.5 A (1 ms)

  • Off‑State Leakage Current: < 0.88 mA RMS @ 230 V AC

  • On‑State Voltage Drop: ≤ 1.5 V RMS

  • dv/dt Rating: 400 V/μs

  • Isolation: 2500 Vrms, 1 min (group‑to‑group & group‑to‑bus)

  • Absolute Maximum Output:

    • 300 Vrms (10 s AC)

    • 400 Vrms (1 cycle AC)

Backplane & Power

  • Backplane Current: 320 mA

  • Power Dissipation: ~12.0 W max

  • Internal Power: Powered by Quantum backplane

Fusing & Diagnostics

  • Fused: No (external fusing required)

  • Diagnostics: No fault LEDs or diagnostic functions


3. I/O & LED Indicators (Front)

  • OUT0 … OUT31 (Green LEDs) – Individual output status (ON = lit)

  • ACTIVE (Green LED) – Bus communication OK

  • Fault LED: None


4. Environmental Specifications

  • Operating Temperature: 0 °C … +60 °C

  • Storage Temperature: −40 °C … +85 °C

  • Relative Humidity: 5% … 95% non‑condensing

  • Altitude: ≤ 2,000 m (standard); up to 5,000 m derated

  • ESD: 4 kV contact / 8 kV air

  • EMI: 10 V/m (80–2000 MHz)

  • Protection Class: IP20


5. Physical & Mechanical

  • Dimensions (W × H × D): 35 × 122 × 52 mm (1 slot)

  • Mounting: Any single slot, hot‑swap compatible

  • Wiring: Screw terminals (field side)

  • Output Grouping: 4 groups × 8 ch (common per group)

  • Field Wire Size: 0.5 … 2.5 mm² (20–14 AWG)


6. Wiring & Connection

Outputs

  • Common: Common per group (4 groups)

  • Output: Switch 20–253 V AC between common and output terminal (per channel)

  • Fuse: External fusing required (4 A max per group)

  • Shielding: Recommended for long cables; ground at one end only

  • Polarity: AC, no polarity sensitivity


7. Software Configuration

Supported software:
  • Unity Pro (recommended)

  • Concept v2.2+

  • ProWORX 32

Configuration:
  1. Add 140DAO85300 (1 slot) to I/O map

  2. Default output address: %Q0 … %Q31 (2 words)

  3. No diagnostic configuration available

  4. Download to CPU


8. Troubleshooting

  • All OUT LEDs OFF: Check backplane, module seating, or ACTIVE LED

  • ACTIVE OFF: Module not recognized; reseat or check backplane

  • OUT LED ON but load not energized: Check external fuse, field wiring, or load

  • Erratic Operation: Poor grounding, noise, or overvoltage


9. Certifications

  • CE (EN 55011, EN 61131‑2)

  • UL 508 / CSA C22.2 No. 142

  • CUL, FM Class I Div 2

  • RoHS compliant


10. Ordering Information

  • 140DAO85300: Standard non‑coated, 32×Triac 20–253V AC, 4×8 Group, Non‑Fused / No Diagnostic (general environment, high‑voltage AC)

  • 140DAO85300C: Conformal coated version (harsh environment)


Get a Quote