140DAO84010
Description
140DAO84010
Modicon Quantum AC Discrete Output Module
16 Isolated Outputs, 20–132 V AC, 47–63 Hz, Triac, Standard Non‑Coating, Non‑Fused, No Diagnostic
English Specification Manual (Full Text, No Images)
1. General Description
Outputs: 16 isolated groups × 1 channel (16‑way independent isolation)
Manufacturer: Schneider Electric
Series: Modicon Quantum (140 Series)
Module Type: AC Discrete Output Module, Triac, 16‑Ch Fully Isolated, Standard Non‑Coating, Non‑Fused, No Diagnostic
Total Outputs: 16 points (fully isolated)
Output Grouping: 16 groups × 1 ch (each channel isolated)
Form Factor: 1 slot, hot‑swappable
Coating: Standard non‑conformal coating
Weight: ~0.49 kg
Key Feature: 16×Isolated Triac Out, 20–132V AC, 47–63Hz, Full Channel Isolation, Non‑Fused, No Diagnostic
Application: 24/48/115V AC loads, machinery, lighting, solenoids, general automation requiring isolation
2. Electrical Specifications
Outputs (16 × Isolated Triac, 20–132 V AC)
Output Type: Solid‑state (triac), zero‑crossing
Operating Voltage: 20–132 V AC
Nominal Voltage: 24 / 48 / 115 V AC
Frequency: 47–63 Hz
Load Current (per channel):
24–115 V AC: 4 A RMS max
Total Module Current: 16 A RMS max (continuous)
Surge Current (per channel):
30 A (1 cycle)
20 A (2 cycles)
Off‑State Leakage Current:
24 V AC: < 1 mA RMS
115 V AC: < 2 mA RMS
On‑State Voltage Drop: ≤ 1.5 V RMS
dv/dt Rating: 400 V/μs
Isolation: 2500 Vrms, 1 min (channel‑to‑channel & channel‑to‑bus)
Absolute Maximum Output:
156 Vrms (continuous)
400 Vrms (1 cycle AC)
Backplane & Power
Backplane Current: 350 mA
Power Dissipation: ~8.0 W max
Internal Power: Powered by Quantum backplane
3. I/O & LED Indicators (Front)
OUT0 … OUT15 (Green LEDs) – Individual output status (ON = lit)
ACTIVE (Green LED) – Bus communication OK
No FUSE LED / No Diagnostic LEDs
4. Environmental Specifications
Operating Temperature: 0 °C … +60 °C
Storage Temperature: −40 °C … +85 °C
Relative Humidity: 5% … 95% non‑condensing
Altitude: ≤ 2,000 m (standard); up to 5,000 m derated
ESD: 4 kV contact / 8 kV air
EMI: 10 V/m (80–2000 MHz)
Protection Class: IP20
5. Physical & Mechanical
Dimensions (W × H × D): 35 × 122 × 52 mm (1 slot)
Mounting: Any single slot, hot‑swap compatible
Wiring: Screw terminals (field side)
Output Grouping: 16 groups × 1 ch (each channel isolated, no common)
Field Wire Size: 0.5 … 2.5 mm² (20–14 AWG)
6. Wiring & Connection
Outputs
Common: No common (fully isolated channels)
Output: Switch 20–132 V AC between two field terminals (per channel)
Fuse: Non‑fused (external protection recommended)
Shielding: Recommended for long cables; ground at one end only
Polarity: AC, no polarity sensitivity
7. Software Configuration
Unity Pro (recommended)
Concept v2.2+
ProWORX 32
Add 140DAO84010 (1 slot) to I/O map
Default output address: %Q0 … %Q15 (1 word)
Set output filter (optional)
Download to CPU
8. Troubleshooting
All OUT LEDs OFF: Check backplane, module seating, or ACTIVE LED
ACTIVE OFF: Module not recognized; reseat or check backplane
OUT LED ON but load not energized: Check field wiring, load, or external fuse
Erratic Operation: Poor grounding, noise, or overvoltage
Leakage Current Issues: Use snubbers for high‑impedance loads
9. Certifications
CE (EN 55011, EN 61131‑2)
UL 508 / CSA C22.2 No. 142
CUL, FM Class I Div 2
RoHS compliant
10. Ordering Information
140DAO84010: Standard non‑coated, 16×Isolated Triac 20–132V AC, Non‑Fused / No Diagnostic (general environment)
140DAO84010C: Conformal coated, 16×Isolated Triac 20–132V AC, Non‑Fused / No Diagnostic (harsh environment)
Get a Quote