140DAO84000
May 16, 2026

140DAO84000

140DAO84000 Modicon Quantum AC Discrete Output Module

Description

140DAO84000

Modicon Quantum AC Discrete Output Module

16 Isolated Outputs, 20–253 V AC, 47–63 Hz, Triac, Standard Non‑Coating, Non‑Fused, No Diagnostic

English Specification Manual (Full Text, No Images)


1. General Description

140DAO84000 is a 1‑slot standard AC discrete output module (triac, isolated, non‑fused, non‑diagnostic) for Schneider Electric Modicon Quantum PLC. It provides 16 fully isolated AC solid‑state (triac) output channels, arranged as:
  • Outputs: 16 isolated groups × 1 channel (16‑way independent isolation)

Designed for universal AC output applications (24/115/230V AC) requiring full channel‑to‑channel isolation, high voltage tolerance, and solid‑state reliability, without on‑board diagnostics or group fuses.
  • Manufacturer: Schneider Electric

  • Series: Modicon Quantum (140 Series)

  • Module Type: AC Discrete Output Module, Triac, 16‑Ch Isolated, Standard, Non‑Fused, No Diagnostic

  • Total Outputs: 16 points (fully isolated)

  • Output Grouping: 16 groups × 1 ch (each channel isolated)

  • Form Factor: 1 slot, hot‑swappable

  • Coating: Standard non‑conformal coating

  • Weight: ~0.50 kg

  • Key Feature: 16×Isolated Triac Out, 20–253V AC, 47–63Hz, Full Channel Isolation, Non‑Fused, No Diagnostic

  • Application: General automation, machinery, lighting, heaters, valves, 24/115/230V AC loads requiring isolation


2. Electrical Specifications

Outputs (16 × Isolated Triac, 20–253 V AC)

  • Output Type: Solid‑state (triac), zero‑crossing

  • Operating Voltage: 20–253 V AC

  • Nominal Voltage: 24 / 48 / 115 / 230 V AC

  • Frequency: 47–63 Hz

  • Load Current (per channel):

    • 24–115 V AC: 4 A RMS max

    • 200–230 V AC: 3 A RMS max

  • Total Module Current: 16 A RMS max (continuous)

  • Surge Current (per channel):

    • 30 A (1 cycle)

    • 20 A (2 cycles)

  • Off‑State Leakage Current:

    • 24 V AC: < 1 mA RMS

    • 115 V AC: < 2 mA RMS

    • 230 V AC: < 2.5 mA RMS

  • On‑State Voltage Drop: ≤ 1.5 V RMS

  • dv/dt Rating: 400 V/μs

  • Isolation: 2500 Vrms, 1 min (channel‑to‑channel & channel‑to‑bus)

  • Absolute Maximum Output:

    • 400 Vrms (1 cycle AC)

    • 300 Vrms (10 s AC)

Backplane & Power

  • Backplane Current: 350 mA

  • Power Dissipation: ~8.0 W max

  • Internal Power: Powered by Quantum backplane


3. I/O & LED Indicators (Front)

  • OUT0 … OUT15 (Green LEDs) – Individual output status (ON = lit)

  • ACTIVE (Green LED) – Bus communication OK

  • No FUSE LED / No Diagnostic LEDs


4. Environmental Specifications

  • Operating Temperature: 0 °C … +60 °C

  • Storage Temperature: −40 °C … +85 °C

  • Relative Humidity: 5% … 95% non‑condensing

  • Altitude: ≤ 2,000 m (standard); up to 5,000 m derated

  • ESD: 4 kV contact / 8 kV air

  • EMI: 10 V/m (80–2000 MHz)

  • Protection Class: IP20


5. Physical & Mechanical

  • Dimensions (W × H × D): 35 × 122 × 52 mm (1 slot)

  • Mounting: Any single slot, hot‑swap compatible

  • Wiring: Screw terminals (field side)

  • Output Grouping: 16 groups × 1 ch (each channel isolated, no common)

  • Field Wire Size: 0.5 … 2.5 mm² (20–14 AWG)


6. Wiring & Connection

Outputs

  • Common: No common (fully isolated channels)

  • Output: Switch 20–253 V AC between two field terminals (per channel)

  • Fuse: Non‑fused (external protection recommended)

  • Shielding: Recommended for long cables; ground at one end only

  • Polarity: AC, no polarity sensitivity


7. Software Configuration

Supported software:
  • Unity Pro (recommended)

  • Concept v2.2+

  • ProWORX 32

Configuration:
  1. Add 140DAO84000 (1 slot) to I/O map

  2. Default output address: %Q0 … %Q15 (1 word)

  3. Set output filter (optional)

  4. Download to CPU


8. Troubleshooting

  • All OUT LEDs OFF: Check backplane, module seating, or ACTIVE LED

  • ACTIVE OFF: Module not recognized; reseat or check backplane

  • OUT LED ON but load not energized: Check field wiring, load, or external fuse

  • Erratic Operation: Poor grounding, noise, or overvoltage

  • Leakage Current Issues: Use snubbers for high‑impedance loads


9. Certifications

  • CE (EN 55011, EN 61131‑2)

  • UL 508 / CSA C22.2 No. 142

  • CUL, FM Class I Div 2

  • RoHS compliant


10. Ordering Information

  • 140DAO84000: Standard non‑coated, Isolated Triac, Non‑Fused / No Diagnostic (general environment)

  • 140DAO84000C: Conformal coated, Isolated Triac, Non‑Fused / No Diagnostic (harsh


Get a Quote